«Collective» detection lines can only be installed as stub lines. According to the type of
control unit or regulations, 20...32 fire detectors can be connected per stub line.
New systems: Twisted cable, in exceptional cases with very powerful electromagnetic
influence shielded and twisted.
Existing systems: Single and parallel conductors are permissible.
Line resistances and line capacitances see document e1508 «Connection factors, line
resistances and capacitances».
Type of cable
Application
Twisted, min. 7 turns
Generally recommended
Shielded, twisted
Essential in areas where EMI is critical
min. 7 turns
e.g. X-ray rooms, radar systems, transmitter stations, proximity to thy-
ristor controls etc.
Non-twisted
Cable in existing systems can be utilized without difficulty with mini-
mum remaining risk
Not recommended for new systems
Shielded/non-twisted
Cable in existing systems can be utilized without difficulty with mini-
mum remaining risk
Not recommended for new systems