Plume Management Options & Measurement - Bosch WORCESTER Condensfit II GREENSTAR 60/100 HORIZONTAL FLUE Installation Manual

Flue kit for worcester greenstar cdi wall hung, si, i junior, i system & ri series of gas appliances including british gas variants
Table of Contents

Advertisement

6.2
PLUME MANAGEMENT OPTIONS &
MEASUREMENT
NOTE: PLUME MANAGEMENT
B All plume management sections must rise
away from the terminal by a minimum of
173mm per metre (10°) to allow the
condensate to drain back to the boiler.
The figure 28 shows the components required for typical
plume management configurations.
PLUME MANAGEMENT KIT
1
3
4
2
Fig. 28
Plume management components
1
Terminal bend
2
Extension 500mm
3
Outlet assembly
4
Clamp
Table 14 Key to figure 28
PLUME MANAGEMENT OPTIONAL KIT
1
3
2
4
5
6720644842-17.1Wo
Fig. 29
Optional components
5
Extension tube 100mm and Clamp
6
90° Bend
7
45° Bend
Table 15 Key to figure 29
6 720 644 842b (2010/12)
6720644842-16.1Wo
1
3
2
4
5
7
6720644842-18.1Wo
Fig. 30
Plume management with bend
1
4
Fig. 31
Plume management with straight extension
NOTE: PLUME MANAGEMENT LENGTH
B Measurement M must be a minimum of
500mm and must not exceed the
maximum straight length for a horizontal
Ø 60/100mm flue or a 60mm plume
management system as stated in the
relevant appliance Installation,
commissioning and service manual or
addendum.
PRE-INSTALLATION
3
2
5
5
6720644842-19.1Wo
17