Extended Plume Management Installation - Bosch WORCESTER Condensfit II GREENSTAR 60/100 HORIZONTAL FLUE Installation Manual

Flue kit for worcester greenstar cdi wall hung, si, i junior, i system & ri series of gas appliances including british gas variants
Table of Contents

Advertisement

7.2
EXTENDED PLUME MANAGEMENT
INSTALLATION
To ease assembly of the flue components,
lightly grease the seals with the solvent-free
grease supplied.
Check all the seals are properly seated in
the grooves provided and are in good
condition.
All flue joints must be sealed to prevent
leakage of condensate and flue products.
NOTE: PLUME MANAGEMENT
B All plume management sections must rise
away from the terminal by a minimum of
173mm per metre (10°) to allow the
condensate to drain back to the boiler.
FITTING THE EXTENDED PLUME MANAGEMENT:
1. Refer to figure 36 and remove and retain the screws
securing the terminal end and discard the terminal
end.
2. Fit the terminal bend to the terminal outlet and secure
with the screws retained earlier.
3. If required, rotate the terminal bend for angled fluing.
NOTE: DO NOT ROTATE THE COMPLETE
FLUE TERMINAL ASSEMBLY.
B The flue terminal outlet has built-in stops
to limit rotation for horizontal fluing to
allow condensate to run back to the
boiler for safe disposal.
Do not attempt to force beyond the limit
stops.
6 720 644 842b (2010/12)
Refer to figure 38 and assemble the plume extensions.
1. Mark the position for the wall clamp that coincides
with the extension tube, as shown.
Drill a suitable hole and fit the wall plug.
Screw the clamp into the wall plug as shown.
2. Push the extension tube fully into the terminal bend,
then withdraw the tube by approximately 10mm to
allow for expansion.
3. Secure the extension to the wall with the clamp and
screws provided.
4. Mount the other extension tubes as before and secure
to the wall
5. Push the outlet assembly fully into the extension tube.
6. Rotate the outlet assembly to the required direction
and secure the outlet to the extension with the self-
tapping screw provided.
3.
65 mm
1.
2.
10 mm
Fig. 38
Plume extensions
INSTALLATION
±45°
4.
5.
6.
1.
3.
2.
2.
1.
3.
2.
±80°
6720644842-25.1Wo
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents