Chapter 7 Module Control

7.2 Reset PF Module

7.3 Activate PF Module

7
24
This code is used to reset the PF module from an application when the PF module aborts
for some reason.
Refer to the PF module RAS information in the next chapter and perform the following
procedure.
(1) Check that the PF module Healthy counter is changed. (If it is not changed, this
request is not accepted.)
(2) Write A5A5h in the PF module control enable flag.
(3) Write 0001h in the PF module control code.
(4) After reset completes, check that the PF module status is STANDBY.
The PF module control enable flag and the PF module control code are cleared when
the PF module processes this request.
This code is used to start PF module transmission.
Refer to the PF module RAS information in the next chapter and perform the following
procedure.
(1) Check that the PF module Healthy counter is changed. (If it is not changed, this
request is not accepted.)
(2) Write A5A5h in the PF module control enable flag.
(3) Write 0002h in the PF module control code.
(4) After reset completes, check that the PF module status is ONLINE.
The PF module control enable flag and the PF module control code are cleared when
the PF module processes this request.
If resume transmission (resume transmission with 0 data or data prior to error
occurrence) is selected for PF module operation setting when there is a controller
error, activate PF module request is ignored and transmission is started when
controller error is resolved.