Fastening the
Shipping Split to the
Floor

Fastening Clamps

Dimensions of the fastening clamp
ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
Fastening the shipping split to the floor is especially important in
installations subjected to vibration or other movement.
Insert the clamp into the longitudinal hole in the edge of the cabinet
frame body and fasten it with a bolt to the floor. Allowed maximum
distance between the fastening clamps is 800 mm.
Cabinet frame body
Cabinet frame body
Chapter 2 – Mechanical Installation
Fastening hole distances for the common cabinet are given
below. Fastening bolt: M10 to M12 (3/8" to 1/2").
Cubicle Width
200
400
600
800
1000
a: 350, b: 150, a: 350
1500
a: 350, b: 150, a: 350, b: 150, a: 350
Hole Distance (mm)
a
b
a
46
a: 250
a: 450
a: 650
2-7