Inverter Modules R6I And R7I - ABB ACA 6 Series Hardware Manual

Frequency converters 3 to 4300 kw
Table of Contents

Advertisement

Inverter Modules R6i
and R7i (ACS 600
MultiDrive)
F10
Control cable connection:
Connect the control cables to the appropriate
terminal block on the DIN rail.
ACA 6xx Sections and ACS/ACC 6x7 (132 to 3000 kW) Frequency Converters
The cable connections of a bottom entry unit are represented below.
For top exit, an extra cabinet is required (200 mm to 800 mm, see page
3-21).
Chapter 3 – Electrical Installation
Motor cable connection
1. Strip the cable 3 cm at the cabinet
entry if EMC sleeves are used.
2. Lead the cable unstripped to the
busbar terminals behind the fan.
3. Connect the cables to the
terminals with cable lugs.
4. Connect the shield conductor to
the PE busbar.
Busbars for motor
cable connection:
U2, V2, W2.
Motor cables
PE terminal of
the cabinet
3-19