ABB AC500 Series Installation Instructions Manual page 48

Hide thumbs Also See for AC500 Series:
Table of Contents

Advertisement

AX521
Device
AI523 (-XC)
AI531
AI531-XC
AI561
AI562
AI563
AO523 (-XC)
AO561
AX521 (-XC)
AX522 (-XC)
AX561
CD522 (-XC)
DA501 (-XC)
DC522 (-XC)
DC523 (-XC)
DC532 (-XC)
DC561
DC562
DI524 (-XC)
DI561
DI562
DI571
DI572
DO524 (-XC)
DO526
DO526-XC
DO561
DO562
DO571
48
NOTICE!
Risk of damage to I/O modules!
Do not perform hot swapping if any I/O module with firmware version lower than
3.0.14 is part of the I/O configuration.
For min. required device index see table below.
Hot swapping is only allowed for I/O modules.
Processor modules and communication interface modules must not be removed
or inserted during operation.
3ADR024117M02xx, 11, en_US
Min. required device index for I/O module as of
FW Version 3.0.14
D2
D4
D2
B2
B2
B3
D2
B2
D2
D2
B2
D1
D2
D2
D2
D2
B2
A2
D2
B2
B2
B2
A1
A3
A2
A0
B2
A2
B3
2019/11/15

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents