Siemens PAD-5-CLSA Installation Manual
Siemens PAD-5-CLSA Installation Manual

Siemens PAD-5-CLSA Installation Manual

Class a/b expansion board with releasing
Hide thumbs Also See for PAD-5-CLSA:

Advertisement

Model PAD-5
-CLSA
TM
Class A/B Expansion Board
with Releasing
Installation
Siemens Industry, Inc.
A6V101030359_en--_c
Building Technologies Division

Advertisement

Table of Contents
loading

Summary of Contents for Siemens PAD-5-CLSA

  • Page 1 Model PAD-5 -CLSA Class A/B Expansion Board with Releasing Installation Siemens Industry, Inc. A6V101030359_en--_c Building Technologies Division...
  • Page 2 Technical specifications and availability subject to change without notice. © 2019 Copyright by Siemens Industry, Inc. PAD-5 is a trademark of Siemens Industry, Inc. Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited.
  • Page 3 In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art security concept. Siemens’ portfolio only forms one element of such a concept. You are responsible for preventing unauthorized access to your plants, systems,...
  • Page 4: Table Of Contents

        Wire Routing ......................8     Wiring the PAD-5-CLSA ..................9     Wiring and Configuring the PAD-5-CLSA............. 9     NAC Circuits ....................... 11     3.2.1 Wiring the NAC circuits – Class A and B  ...
  • Page 5: Pad-5-Clsa

    Figure 1: PAD-5-CLSA Description The Model PAD-5-CLSA is an add-on card for the PAD-5 Main Board. When mounted on the main board, this add-on card provides four additional NAC circuits that can be configured for Releasing as well as other configurable properties as described below.
  • Page 6: Properties

    Model PAD-5-CLSA Properties  There are four power limited NAC outputs which have the following characteristics: - NAC 5 through NAC 8 (Wiring configuration Class B or Class A). In Class A, the NACs are referred to as NAC 3 and NAC 4.
  • Page 7: Installation

    PAD-5-CLSA with the two connectors on the main board. 6. Use the two 13/16” screws provided to secure the board in place. 7. Attach screw “A” to the PAD-5-CLSA board and the male-female standoff as shown in Figure 2. Siemens Industry, Inc.
  • Page 8: Wire Routing

    Model PAD-5-CLSA CAUTION: It is recommended that the printed circuit boards be removed for any procedure that may cause dust, metal shavings, grease, or any such matter that may affect the cir- cuit boards and/or parts. All field wiring and connections to the PAD-5-MB must be disconnected, and AC must be disconnected before unscrewing and removing the board assembly from the enclosure.
  • Page 9: Wiring The Pad-5-Clsa

    Model PAD-5-CLSA Wiring and Configuring the PAD-5-CLSA Knockout Locations A. Non-Power Limited - High Voltage (AC power) B. Power Limited C. Power Limited D. Power Limited E. Power Limited 3 Wiring the PAD-5-CLSA Wiring and Configuring the PAD-5-CLSA The chart below identifies the relevant elements and their location on the PAD-5- CLSA.
  • Page 10 Model PAD-5-CLSA Wiring and Configuring the PAD-5-CLSA Element Des. Function Indicators H200 NAC 5 STATUS H202 NAC 6 STATUS H201 NAC 7 STATUS H203 NAC 8 STATUS Programming X501, X502 DPU Address Programming Holes X200 Serial Debug/Firmware Programming Port Main processor...
  • Page 11: Nac Circuits

    Model PAD-5-CLSA NAC Circuits 3.2.1 Wiring the NAC circuits – Class A and B Notification appliance circuit supervised and power limited. Maximum output current of any NAC, regardless of class, is 3A CLASS A EO L EO L CLASS B Figure 5: NAC 5 and 6 shown configured as one Class A loop, and NAC 7 and 8 shown configured as two Class B loops (supervised output connection.
  • Page 12: Nacs Configured As Auxiliary Output Circuits

    Model PAD-5-CLSA NAC Circuits X300 Designation Description Positive feed for notification appliances for NAC 3 class A or NAC 5 class B Return feed for notification appliances for NAC 3 class A or NAC 5 class B Positive feed for notification appliances for NAC 3 class A or NAC 6 class B Return feed for notification appliances for NAC 3 class A or NAC 6 class B Admissible cable cross-section: 1 x 12…18 AWG or 2 x 16…18 AWG...
  • Page 13: Nacs Configured As Shorting Device Inputs

    Model PAD-5-CLSA NAC Circuits X400 Designation Description Positive feed for Auxiliary Circuit 7 (DC +24 V) Return feed for Auxiliary Circuit 7 (DC -24 V) Positive feed for Auxiliary Circuit 8 (DC +24 V) Return feed for Auxiliary Circuit 8 (DC -24 V) Admissible cable cross-section: 1 x 12-18 AWG or 2 x 16-18 A 3.2.3...
  • Page 14: Releasing Application

    Model PAD-5-CLSA NAC Circuits 4 Releasing Application WARNING: For releasing applications, we recommend that circuit 7 and 8 are not utilized for AUX power or NAC circuits. Only to be utilized as input circuits. NOTE: For Releasing Applications, the minimum battery size that can be used is 18 Ah (BP-61) NOTE: Refer to the Solenoid Compatibility List, Document ID A6V11620059.
  • Page 15: Wiring Class B Releasing

    NOTE 2: LOOP WIRES SHOULD BE TERMINATED DIRECTLY AT THE SOLENOID. Polarity shown in ACTIVE mode REL-EOL: Terminating resistor 24kΩ and diode (Siemens P/N 500-696359) Maximum length of line of the relay connections is limited to a resistance of 3.5Ω Figure 8: Wiring Class A Releasing Siemens Industry, Inc.
  • Page 16: Synchronization Of Strobes

    Model PAD-5-CLSA Synchronization of Strobes NACs 5-8 have the same functionality as NACs 1-4. So configuring for synchronization is done through the Zeus programming tool. Since the NACs are all part of the same PAD-5-MB, they will always be synchronized with each other. For multiple PAD-5-MBs requiring synchronization, refer to the PAD-5-MB instructions, section 3.2.2.1...
  • Page 17: Switches

    Model PAD-5-CLSA LED Indicators Color Condition Meaning H204 Yellow Blinking Indicates main microprocessor is processing data H501 Yellow P2 - Normal condition P2 - Trouble Condition H500 Green P2 – Pattern not Locatable P2 – Pattern Locate 4.4.1 Switches 4.4.1.1...
  • Page 18 Model PAD-5-CLSA LED Indicators 4.4.1.4 S600, S601 Releasing Configuration Switch Button Function Position Meaning S600 Enables/Disables Releasing -Releasing Zone 1 configured for Zone 1 releasing NAC5 configured for NAC S601 Enables/Disables Releasing -Releasing Zone 2 configured for Zone 2 releasing NAC6 configured for NAC Siemens Industry, Inc.
  • Page 19: Technical Data

    Model PAD-5-CLSA Technical Data Technical Data Supply input Operating voltage DC 26 V nominal, filtered DC 3.3V nominal, filtered Operating current (standby) 55mA Max. operating current. 6.0 A NAC circuit Plug strip X300, X400 Voltage DC 24 V Special Application for strobe loads...
  • Page 20 Issued by © 2019 Siemens Industry, Inc. Siemens Industry, Inc. Technical specifications and availability subject to change without notice. Building Technologies Division 8 Fernwood Road Florham Park, NJ 07932 Tel. +1 973-593-2600 www.sbt.siemens.com/FIS Document ID A6V101030359_en--_c P/N A5Q00072306...