BACnet points of PAHCMR000 (Return air temperature control)

n AHU Control / Monitor point
No.
Name
1
ON/OFF (Setting)
2
ON/OFF (Status)
3
Lock (Setting)
4
Lock (Status)
5
Operation Mode (Setting)
6
Operation Mode (Status)
1)
7
Fan Speed (Setting)
1)
8
Fan Speed (Status)
9
Set Room Temperature
10
Room Temperature
11
Alarm
12
Error Code
13
Set Temperature (Status)
14
Set Upper Temperature (Setting) ac_TempRangeUpperLi m i t Command_XX
15
Set Lower Temperature (Setting) ac_TempRangeLowerLi m i t Command_XX
16
Set Upper Temperature (Status)
17
Set Lower Temperature (Status)
18
Mode Lock (Setting)
19
Mode Lock (Status)
20
Fan Lock (Setting)
21
Fan Lock (Status)
22
Thermal Status (Status)
NOTE
• ACP BACnet gateway is required for BACnet protocol.
• In case of PAHCMS000, BACnet protocol is not supported.
• For more details, refer to the manual of control product.
- For fan speed control, it is necessary to set DIP SW 1-3 'ON'.
Object Name
(XX : Unit Address
Number)
ac_StartStopCommand_XX
ac_StartStopStatus_XX
ac_LockCommand_XX
ac_LockStatus_XX
ac_AirConModeCommand_XX
ac_AirConModeStatus_XX
ac_FanSpeedCommand_XX
ac_FanSpeedStatus_XX
ac_SetRoomTemp_XX
ac_RoomTemp_XX
ac_Alarm_XX
ac_MalfunctionCode_XX
ac_SetTempStatus_XX
ac_TempRangeUpperLi m i t Status_XX
ac_TempRangeLowerLi m i t Status_XX
ac_ModeLockCommand_XX
ac_ModeLockStatus_XX
ac_FanLockCommand_XX
ac_FanLockStatus_XX
ac_ThermoStatus_XX
Object
Inactive
Type
TEXT-0 TEXT-1 TEXT-2 TEXT-3 TEXT-4 TEXT-5
BO
Stop(0) Start(1)
BI
Stop(0) Start(1)
BO
Permit(0) Prohibit(1)
BI
Permit(0) Prohibit(1)
MO
Cool(1)
MI
Cool(1)
MO
Low(1) Middle(2) High(3)
MI
Low(1) Middle(2) High(3)
AV
°C(16~30 °C)
AI
°C(-99~99 °C)
BI
Normal(0) Abnormal(1)
AI
0~255 (Refer to the LG Error code list)
AI
°C(16~30 °C)
AV
°C(16~30 °C)
AV
°C(16~30 °C)
AI
°C(16~30 °C)
AI
°C(16~30 °C)
BO
Permit(0) Prohibit(1)
BI
Permit(0) Prohibit(1)
BO
Permit(0) Prohibit(1)
BI
Permit(0) Prohibit(1)
BI
OFF(0)
ON(1)
BMS PROTOCOL
35
Unit
Active
Fan(3)
Heat(5)
Fan(3)
Heat(5)

Hide quick links: