Siemens SIMATIC S7-1500 Manual page 23

Digital input/output module di 16x24vdc/dq 16x24vdc/0.5a ba
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Meaning of the LED displays
The tables below explain the meaning of the status and error displays.
LED RUN/ERROR
Table 5- 1
RUN/ERROR status and error displays
LED
RUN
ERROR
Off
Off
Flashes
Off
On
Off
Flashes
Flashes
LED PWRx
Table 5- 2
PWRx status display
LED PWRx
Off
On
LED CHx
Table 5- 3
CHx status display
LED CHx
Off
On
Digital input/output module DI 16x24VDC/DQ 16x24VDC/0.5A BA (6ES7523-1BL00-0AA0)
Manual, 09/2014, A5E32364588-AB
Meaning
Voltage missing or too low at backplane bus.
Module is starting up.
Module is ready.
Hardware defective.
Meaning
Supply voltage L+ too low or missing
Supply voltage L+ is present and OK.
Meaning
0 = Status of the input/output signal.
1 = Status of the input/output signal.
5.1 Status and error displays
Remedy
Switch on the CPU and/or the system pow-
er supply modules.
Verify that the U connectors are inserted.
Check to see if too many modules are in-
serted.
---
Replace the module.
Remedy
Check supply voltage L+.
---
Remedy
---
---