Other control cable types
There are two types of data cable commonly used to connect to electronic drivers with LEDs or fluorescent
lamps.
1-10V cabling
1-10V mains rated polarized cabling. Single pair figure-eight cable. Positive wire with dashed line.
DALI Cabling
DALI (and DSI) mains rated non-polarized cabling. Single pair figure-eight cable. Maximum bus length of 300 m
(1000 ft). Maximum 2 V voltage drop between any two DALI devices.
DALI is not touch-safe and shall be treated as ELV per IEC Classification. DALI could be mains potential.
B
Only basic isolation is provided. The DALI control cable must be handled as live up to 230VAC.
Total loop resistance on longest run < 18 Ohms. The cable run distance from any point to the DALI controller
should not exceed 300 m (1000 ft).
Wire gauge
1.5 mm
2
(16 AWG)
0.75 mm
2
(18 AWG)
0.5 mm
(20 AWG)
2
14
th
November 2019
Maximum cable distance
150 to 300 m (500 to 1000 ft) Typical
Between 100 to 150 m (330 to 500 ft)
Up to 100 m (330 ft)
Dynalite Hardware
.......................................
Installation Guide
.......................................
Page 5
.......................................
www.philips.com/dynalite