A Technical Specifications - Huawei ECC500 User Manual

Data center
Hide thumbs Also See for ECC500:
Table of Contents

Advertisement

ECC500 (Data Center)
User Manual
Table A-1
Table A-1 ECC technical specifications
Category
Environment
Power supply
input
EMC
Issue 06 (2020-01-06)
A
lists ECC500 technical specifications.
Item
Operating temperature
Storage temperature
Humidity
Atmospheric pressure
Altitude
Moisture resistance
Others
Operating voltage
Operating power
Conducted interference
Radiated interference
Electrostatic interference
Copyright © Huawei Technologies Co., Ltd.
Technical Specifications

A Technical Specifications

Description
—40° C to +70° C
—45° C to +70° C
5%-95% RH (non-condensing)
70-106 kPa
When the altitude is less than or
equal to 3000 m, the ECC500
works properly
When the altitude is greater than
3000 m, the temperature
decreases by 1° C for each
additional 300 m
Damp heat, cyclic: 25—65° C,
95% RH, 48 hours
Free from explosives, conductive
dust, and corrosive air
Operating voltage: —40 V DC to
—60 V DC
Rated voltage: —48 V DC
Rated power: 30 W
Class B
Class B
For the shell: contact
discharge: ± 6 kV; air
discharge: ± 8 kV (criterion B);
the shell has been powered on
53