PDU8000 Modular Precision PDC
User Manual (FusionModule2000 V2.0)
Figure 8-3 Detecting the voltages
Step 4 Hold the faulty SPD and pull it out.
Figure 8-4 Replacing an SPD Module
Step 5 Install a new SPD module.
Step 6 Switch on the SPD circuit breaker.
Step 7 Reinstall the protective panel.
----End
8.5.2 Replacing an Indicator
Prerequisites
Issue 02 (2017-02-24)
If there is a faulty surge protection module, it is recommended that all surge protection modules be
replaced.
If the SPD module cannot be pulled out, use a tool such as a flat-head screwdriver to lever it out.
Tools required: an electrical tester pen, Phillips screwdriver, key to the PDC cabinet door,
multimeter, step ladder, and a pair of insulating gloves
Material required: a spare functional indicator with the same model
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance Guide
133