Relion
620 series
Advanced Recloser Protection and Control
RER620
IEC 60870-5-101/104 Point List Manual

Advertisement

Table of Contents
loading

Summary of Contents for ABB Relion 620 Series

  • Page 1 ® Relion 620 series Advanced Recloser Protection and Control RER620 IEC 60870-5-101/104 Point List Manual...
  • Page 3 Document ID: 1MAC302441-MB Issued: 11/23/2010 Revision: A Product version: 1.0 © Copyright 2010 ABB. All rights reserved.
  • Page 4 Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
  • Page 5 This document has been carefully checked by ABB but deviations cannot be completely ruled out. In case any errors are detected, the reader is kindly requested to notify the manufacturer.
  • Page 6 (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the directive, and with the product standards EN 60255-6 and EN 60255-27 for the directive.
  • Page 7: Table Of Contents

    Table of contents 1MAC302441-MB A Table of contents Section 1 Introduction................3 This manual....................3 Intended audience..................3 Product documentation ................4 Product documentation set ..............4 Document revision history..............5 Related documentation ............... 5 Symbols and conventions ................ 5 Safety indication symbols..............
  • Page 8 Table of contents 1MAC302441-MB A RER620 Point List Manual...
  • Page 9: Introduction

    Section 1 1MAC302441-MB A Introduction Section 1 Introduction This manual The point list manual describes the outlook and properties of the data points specific to the IED. The manual should be used in conjunction with the corresponding communication protocol manual. Intended audience This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation...
  • Page 10: Product Documentation

    Section 1 1MAC302441-MB A Introduction Product documentation 1.3.1 Product documentation set Application manual Engineering manual Installation manual Operation manual Technical manual Communication Protocol manual Protocol Points List manual Figure 1: The intended use of manuals in different lifecycles The engineering manual contains instructions on how to engineer the IED using the different tools in PCM600.
  • Page 11: Document Revision History

    1.3.2 Document revision history Document revision/date Product version History A/11/23/2010 First release Download the latest documents from the ABB web site http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID IEC 60870-5-101/104 Communication Protocol Manual 1MAC306892-MB Symbols and conventions 1.4.1...
  • Page 12: Manual Conventions

    Section 1 1MAC302441-MB A Introduction 1.4.2 Manual conventions Conventions used in IED manuals. A particular convention may not be used in this manual. • Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions of important terms. •...
  • Page 13: Functions, Codes And Symbols

    Section 1 1MAC302441-MB A Introduction 1.4.3 Functions, codes and symbols Table 1: RER620 functions, codes and symbols Function IEC61850 IEC60617 ANSI/C37.2 Current Protection Single-phase non-directional time overcurrent protection with 1-ph trip option, low stage SPHLPTOC1 3I>(1) Single-phase non-directional time overcurrent protection with 1-ph trip option, high stage 1 SPHLPTOC2 3I>(2) 50P-1...
  • Page 14 Section 1 1MAC302441-MB A Introduction Function IEC61850 IEC60617 ANSI/C37.2 Zero sequence overvoltage protection, source 2 ROVPTOV2 Uo>(2) 59N-2 Frequency Protection Underfrequency, Overfrequency, Frequency rate of change, source1 FRPFRQ1 f</f>,df/dt(1) 81-1 Underfrequency, Overfrequency, Frequency rate of change, source 2 FRPFRQ2 f</f>,df/dt(2) 81-2 Load Shed &...
  • Page 15 Section 1 1MAC302441-MB A Introduction Function IEC61850 IEC60617 ANSI/C37.2 Move function block (8 outputs) MVGAPC2 MVGAPC2 MVGAPC2 Pulse timer (8 timers) PTGAPC1 PTGAPC1 PTGAPC1 Pulse timer (8 timers) PTGAPC2 PTGAPC2 PTGAPC2 Generic control points (16 outputs) SPCGGIO1 SPCGGIO1 SPCGGIO1 Generic control points (16 outputs) SPCGGIO2 SPCGGIO2 SPCGGIO2...
  • Page 16 Section 1 1MAC302441-MB A Introduction RER620 Point List Manual...
  • Page 17: Iec 60870-5-101/104 Data Mappings

    Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Section 2 IEC 60870-5-101/104 data mappings Overview This document describes the IEC 60870-5-101/104 data points and structures available in RER620 Ver. 1.0. The point tables show all the available IEC 60870-5-101/104 data points in this IED. The points are grouped into four tables: Analog Values, Binary Controls, Indications, and Integrated Totals and Regulating Step Positions.
  • Page 18: Point List For Rer620 Ver. 1.0

    Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Point list for RER620 Ver. 1.0 Table 2: Analog values No events 61850 Path Disabled Description Multiplier Interrogation CMMXU1.A.phsA.cVal.mag.f 8000 "IA,IB,IC:phase A amplitude" CMMXU1.A.phsA.instCVal.ang.f 8001 "IA,IB,IC:phase A angle" CMMXU1.A.phsB.cVal.mag.f 8003 "IA,IB,IC:phase B amplitude" CMMXU1.A.phsB.instCVal.ang.f 8004 "IA,IB,IC:phase B angle"...
  • Page 19 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation VMMXU1.PPV.phsCA.cVal.mag.f 8058 "VA,VB,VC:phase CA amplitude" VMMXU1.PPV.phsCA.instCVal.ang.f 8059 "VA,VB,VC:phase CA angle" VMMXU2.PhV.phsA.cVal.ang.f 8061 "VA,VB,VC(2):phase A angle" VMMXU2.PhV.phsA.cVal.mag.f 8062 "VA,VB,VC(2):phase A amplitude" VMMXU2.PhV.phsB.cVal.ang.f 8063 "VA,VB,VC(2):phase B angle" VMMXU2.PhV.phsB.cVal.mag.f 8064 "VA,VB,VC(2):phase B amplitude"...
  • Page 20 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation RDRE1.MemUsed.stVal 10112 DFR:MemUsed status SDARREC1.AutoRecSt.stVal 10113 79:AutoRecSt status SDARREC1.ShotPntr.stVal 10114 79:ShotPntr status SPHPTOV1.StrDur.mag.f 10115 59-1:StrDur magnitude SPHPTOV2.StrDur.mag.f 10116 59-2:StrDur magnitude SPHPTOV3.StrDur.mag.f 10117 59-3:StrDur magnitude SPHPTUV1.StrDur.mag.f 10118 27-1:StrDur magnitude...
  • Page 21 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation FLTMSTA1.AmpsC.mag.f 12021 Disabled FLTMSTA1:AmpsC magnitude FLTMSTA1.AmpsN.mag.f 12022 Disabled FLTMSTA1:AmpsN magnitude FLTMSTA1.AmpsNClc.mag.f 12023 Disabled FLTMSTA1:AmpsNClc magnitude FLTMSTA1.AmpsPsSeq.mag.f 12024 Disabled FLTMSTA1:AmpsPsSeq magnitude FLTMSTA1.AmpsNgSeq.mag.f 12025 Disabled FLTMSTA1:AmpsNgSeq magnitude FLTMSTA1.VoltsA.mag.f 12037 Disabled...
  • Page 22 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Table 3: Binary controls No events 61850 Path Disabled Description Multiplier Interrogation LLN0.LEDRs1.Oper.ctlVal 20000 LLN0:LEDRs1 control LLN0.LEDRs2.Oper.ctlVal 20001 LLN0:LEDRs2 control RDRE1.RcdTrg.Oper.ctlVal 20007 DFR:RcdTrg control RDRE1.MemClr.Oper.ctlVal 20008 DFR:MemClr control CMSTA1.RecRs.Oper.ctlVal 20009 CMSTA1:RecRs control LPHD1.RsDev.Oper.ctlVal 20013 LPHD1:RsDev control...
  • Page 23 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SPCGGIO2.SPCSO1.Oper.ctlVal 21130 SPCGGIO2:SPCSO1 control SPCGGIO2.SPCSO10.Oper.ctlVal 21131 SPCGGIO2:SPCSO10 control SPCGGIO2.SPCSO11.Oper.ctlVal 21132 SPCGGIO2:SPCSO11 control SPCGGIO2.SPCSO12.Oper.ctlVal 21133 SPCGGIO2:SPCSO12 control SPCGGIO2.SPCSO13.Oper.ctlVal 21134 SPCGGIO2:SPCSO13 control SPCGGIO2.SPCSO14.Oper.ctlVal 21135 SPCGGIO2:SPCSO14 control SPCGGIO2.SPCSO15.Oper.ctlVal 21136 SPCGGIO2:SPCSO15 control...
  • Page 24 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SRGAPC2.Rs7.Oper.ctlVal 21171 SRGAPC2:Rs7 control SRGAPC2.Rs8.Oper.ctlVal 21172 SRGAPC2:Rs8 control XGGIO100.SPCSO1.Oper.ctlVal 21173 XGGIO100:SPCSO1 control XGGIO100.SPCSO2.Oper.ctlVal 21174 XGGIO100:SPCSO2 control XGGIO100.SPCSO3.Oper.ctlVal 21175 XGGIO100:SPCSO3 control XGGIO100.SPCSO4.Oper.ctlVal 21176 XGGIO100:SPCSO4 control XGGIO100.SPCSO5.Oper.ctlVal 21177 XGGIO100:SPCSO5 control...
  • Page 25 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Table 4: Indications No events 61850 Path Disabled Description Multiplier Interrogation LLN0.Loc.stVal LLN0:Loc status RDRE1.RcdMade.stVal DFR:RcdMade status LLN0.SetSeld.stVal LLN0:SetSeld status LLN0.SetChg.stVal LLN0:SetChg status GSEGGIO1.Alm.stVal GSEGGIO1:Alm status LPHD1.PhyHealth1.stVal Self-supervision / Warning LPHD1.PhyHealth2.stVal Self-supervision / Error LEDPTRC1.Str.general LEDPTRC1:general pickup LEDPTRC1.Str.phsA...
  • Page 26 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation FKEYGGIO1.Ind9.stVal FKEYGGIO1:Ind9 status FKEYGGIO1.Ind10.stVal FKEYGGIO1:Ind10 status FKEYGGIO1.Ind11.stVal FKEYGGIO1:Ind11 status FKEYGGIO1.Ind12.stVal FKEYGGIO1:Ind12 status FKEYGGIO1.Ind13.stVal FKEYGGIO1:Ind13 status FKEYGGIO1.Ind14.stVal FKEYGGIO1:Ind14 status FKEYGGIO1.Ind15.stVal FKEYGGIO1:Ind15 status FKEYGGIO1.Ind16.stVal FKEYGGIO1:Ind16 status DRFLO1.FltLoop.stVal FLO:FltLoop status PTGAPC1.In1.stVal...
  • Page 27 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation TOFGAPC1.In1.stVal TOFGAPC1:In1 status TOFGAPC1.In2.stVal TOFGAPC1:In2 status TOFGAPC1.In3.stVal TOFGAPC1:In3 status TOFGAPC1.In4.stVal TOFGAPC1:In4 status TOFGAPC1.In5.stVal TOFGAPC1:In5 status TOFGAPC1.In6.stVal TOFGAPC1:In6 status TOFGAPC1.In7.stVal TOFGAPC1:In7 status TOFGAPC1.In8.stVal TOFGAPC1:In8 status TOFGAPC1.Q1.stVal TOFGAPC1:Q1 status TOFGAPC1.Q2.stVal...
  • Page 28 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation ZBAT1.SwConnSt.stVal UPS:SwConnSt status ZBAT1.UpsAlmStat.stVal UPS:UpsAlmStat status ZBAT1.UpsTimeDay.stVal UPS:UpsTimeDay status ZBAT1.UpsTimeHr.stVal UPS:UpsTimeHr status ZBAT1.UpsTimeMin.stVal UPS:UpsTimeMin status ZBAT1.UpsTimeSec.stVal UPS:UpsTimeSec status MVGAPC1.Q1.stVal MVGAPC1:Open MVGAPC1.Q2.stVal MVGAPC1:Closed MVGAPC1.Q3.stVal MVGAPC1:Phase A Open MVGAPC1.Q4.stVal MVGAPC1:Phase A Closed MVGAPC1.Q5.stVal...
  • Page 29 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SRGAPC2.Q4.stVal SRGAPC2:Q4 status SRGAPC2.Q5.stVal SRGAPC2:Q5 status SRGAPC2.Q6.stVal SRGAPC2:Q6 status SRGAPC2.Q7.stVal SRGAPC2:Q7 status SRGAPC2.Q8.stVal SRGAPC2:Q8 status SRGAPC2.Set1.stVal SRGAPC2:Set1 status SRGAPC2.Set2.stVal SRGAPC2:Set2 status SRGAPC2.Set3.stVal SRGAPC2:Set3 status SRGAPC2.Set4.stVal SRGAPC2:Set4 status SRGAPC2.Set5.stVal...
  • Page 30 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation TONGAPC2.Q6.stVal TONGAPC2:Q6 status TONGAPC2.Q7.stVal TONGAPC2:Q7 status TONGAPC2.Q8.stVal TONGAPC2:Q8 status DLCM1.BrkSt.stVal LCM:BrkSt status DLCM1.LCMClose.general LCM:Close general DLCM1.LCMTrip.general LCM:Trip general DLCM1.RstIn.stVal LCM:RstIn status DLCM1.RstOut.stVal LCM:RstOut status DLCM1.S1Status.stVal LCM:S1Status status DLCM1.S2Status.stVal...
  • Page 31 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation MVGAPC2.Str.general MVGAPC2:general pickup NSPTOV1.Op.general 47-1:general trip NSPTOV1.Str.general 47-1:general pickup NSPTOV2.Op.general 47-2:general trip NSPTOV2.Str.general 47-2:general pickup PDNSPTOC1.Op.general PDNSPTOC1:general trip PDNSPTOC1.Str.general PDNSPTOC1:general pickup PHIZ1.Op.general 1004 HIZ:general trip PHIZ1.Str.general 1005 HIZ:general pickup...
  • Page 32 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SDARREC1.Op.phsA 1111 79:phase A trip SDARREC1.Op.phsB 1112 79:phase B trip SDARREC1.Op.phsC 1113 79:phase C trip SDARREC1.OpOpn.phsA 1114 79:phase A SDARREC1.OpOpn.phsB 1115 79:phase B SDARREC1.OpOpn.phsC 1116 79:phase C SDPHLPTOC1.Op.general...
  • Page 33 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SPHIPTOC1.Str.phsB 1161 SPHIPTOC1:phase B pickup SPHIPTOC1.Str.phsC 1162 SPHIPTOC1:phase C pickup SPHLPTOC1.Op.general 1163 51P:general trip SPHLPTOC1.Op.phsA 1164 51P:phase A trip SPHLPTOC1.Op.phsB 1165 51P:phase B trip SPHLPTOC1.Op.phsC 1166 51P:phase C trip...
  • Page 34 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation TONGAPC2.Str.general 1213 TONGAPC2:general pickup TPMGAPC1.Op.general 1214 TPMGAPC1:general trip TPMGAPC1.Str.general 1215 TPMGAPC1:general pickup TPMGAPC2.Op.general 1216 TPMGAPC2:general trip TPMGAPC2.Str.general 1217 TPMGAPC2:general pickup TPMGAPC3.Op.general 1218 TPMGAPC3:general trip TPMGAPC3.Str.general 1219 TPMGAPC3:general pickup...
  • Page 35 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SDARREC1.ActRec.stVal 2860 79:ActRec status SDARREC1.PrgDsr.stVal 2861 79:PrgDsr status SDARREC1.PrgCutOut.stVal 2862 79:PrgCutOut status SDARREC1.FrqOpAlm.stVal 2863 79:FrqOpAlm status SDARREC1.CBManCls.stVal 2864 79:CBManCls status SDARREC1.Op.general 2865 79:general trip SDARREC1.OpOpn.general 2866 79:general...
  • Page 36 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SPSCBR1.InSprCha.stVal 3042 52CM:InSprCha status SPSCBR1.InSprChStr.stVal 3043 52CM:InSprChStr status SPSCBR1.LonTmAlm.stVal 3044 52CM:LonTmAlm status SPSCBR1.OpCntA.stVal 3045 52CM:OpCntA status SPSCBR1.OpCntB.stVal 3046 52CM:OpCntB status SPSCBR1.OpCntC.stVal 3047 52CM:OpCntC status SPSCBR1.OpnAlm.stVal 3048 52CM:OpnAlm status...
  • Page 37 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation XGGIO110.Ind3.stVal 5022 XGGIO110:Ind3 status XGGIO110.Ind4.stVal 5023 XGGIO110:Ind4 status XGGIO110.Ind5.stVal 5024 XGGIO110:Ind5 status XGGIO110.Ind6.stVal 5025 XGGIO110:Ind6 status XGGIO110.Ind7.stVal 5026 XGGIO110:Ind7 status XGGIO110.Ind8.stVal 5027 XGGIO110:Ind8 status XGGIO110.SPCSO1.stVal 5030 XGGIO110:SPCSO1 status...
  • Page 38 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SPCGGIO1.SPCSO14.stVal 5103 SPCGGIO1:SPCSO14 status SPCGGIO1.SPCSO15.stVal 5104 SPCGGIO1:SPCSO15 status SPCGGIO1.SPCSO16.stVal 5105 SPCGGIO1:SPCSO16 status FKEYGGIO1.SPCSO1.stVal 5110 FKEYGGIO1:SPCSO1 status FKEYGGIO1.SPCSO2.stVal 5111 FKEYGGIO1:SPCSO2 status FKEYGGIO1.SPCSO3.stVal 5112 FKEYGGIO1:SPCSO3 status FKEYGGIO1.SPCSO4.stVal 5113 FKEYGGIO1:SPCSO4 status...
  • Page 39 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation XGGIO115.InOpnC.stVal 5522 XGGIO115:InOpnC status XGGIO115.LstPoleOp.stVal 5523 XGGIO115:LstPoleOp status XGGIO115.PolSwVol.stVal 5524 XGGIO115:PolSwVol status XGGIO115.Time1.stVal 5525 XGGIO115:Time1 status XGGIO115.Time2.stVal 5526 XGGIO115:Time2 status XGGIO115.Time3.stVal 5527 XGGIO115:Time3 status XGGIO115.Time4.stVal 5528 XGGIO115:Time4 status...
  • Page 40 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation PTGAPC1.Op.general 6237 PTGAPC1:general trip PTGAPC1.Str.general 6238 PTGAPC1:general pickup PTGAPC2.Op.general 6239 PTGAPC2:general trip PTGAPC2.Str.general 6240 PTGAPC2:general pickup ROVPTOV1.Op.general 6241 59N-1:general trip ROVPTOV1.Str.general 6242 59N-1:general pickup ROVPTOV2.Op.general 6243 59N-2:general trip...
  • Page 41 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation SPHIPTOC1.Str.general 6288 SPHIPTOC1:general pickup SPHIPTOC1.Str.phsA 6289 SPHIPTOC1:phase A pickup SPHIPTOC1.Str.phsB 6290 SPHIPTOC1:phase B pickup SPHIPTOC1.Str.phsC 6291 SPHIPTOC1:phase C pickup SPHLPTOC1.Op.general 6292 51P:general trip SPHLPTOC1.Op.phsA 6293 51P:phase A trip SPHLPTOC1.Op.phsB...
  • Page 42 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings No events 61850 Path Disabled Description Multiplier Interrogation TONGAPC1.Str.general 6336 TONGAPC1:general pickup TONGAPC2.Op.general 6337 TONGAPC2:general trip TONGAPC2.Str.general 6338 TONGAPC2:general pickup TPMGAPC1.Op.general 6339 TPMGAPC1:general trip TPMGAPC1.Str.general 6340 TPMGAPC1:general pickup TPMGAPC2.Op.general 6341 TPMGAPC2:general trip TPMGAPC2.Str.general 6342 TPMGAPC2:general pickup...
  • Page 43 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings Table 5: Integrated totals and regulating step positions No events 61850 Path Disabled Description Multiplier Interrogation PEMMTR1.SupWh.actVal 14000 Reverse active energy Wh PEMMTR1.SupVArh.actVal 14001 Reverse reactive energy VArh PEMMTR1.DmdWh.actVal 14002 Forward active energy Wh PEMMTR1.DmdVArh.actVal 14003 Forward reactive energy VArh...
  • Page 44 Section 2 1MAC302441-MB A IEC 60870-5-101/104 data mappings RER620 Point List Manual...
  • Page 45: Iec 60870-5-101/104 Protocol Implementation

    Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Section 3 IEC 60870-5-101/104 protocol implementation This section describes the specific implementation of the IEC 60870-5-101 protocol within the RER620. The RER620 uses the Triangle MicroWorks, Inc. IEC 60870-5-101 Slave Source Code Library Version 3. This section and the documents listed below provide complete information on how to communicate with a RER620 via the IEC 60870-5-101 protocol.
  • Page 46 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation The possible selection (blank, X, R, or B) is specified for each specific Clause or parameter. NOTE: In addition, the full specification of a system may require individual selection of certain parameters for certain parts of the system, such as the individual selection of scaling factors for individually addressable measured values.
  • Page 47 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Transmission speed (monitor direction) Unbalanced interchange Unbalanced interchange Balanced interchange Circuit V.24/V.28 Circuit V.24/V.28 Circuit X.24/X.27 Standard Recommended if >1200 bit/s 100 bit/s 2400 bit/s 2400 bit/s 56000 bit/s 200 bit/s 4800 bit/s 4800 bit/s 64000 bit/s 300 bit/s...
  • Page 48 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation A special assignment of ASDUs to class 2 messages is used as follows: Type Identification Cause of Transmission Note: In response to a class 2 poll, a controlled station may respond with class 1 data when there is no class 2 data available.
  • Page 49 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Selection of standard ASDUs Process information in monitor direction (station-specific parameter, mark each type ID with an “X” if it is only used in the standard direction, “R” if only used in the reverse direction, and “B” if used in both directions) <1>...
  • Page 50 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Process information in control direction (station-specific parameter, mark each type ID with an “X” if it is only used in the standard direction, “R” if only used in the reverse direction, and “B” if used in both directions) <45>...
  • Page 51 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Type identification and cause of transmission assignments (station-specific parameters) Shaded boxes are not required. Blank = function or ASDU is not used. Mark type identification/cause of transmission combinations: “X” if used only in the standard direction; “R”...
  • Page 52 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Cause of transmission Type identification <36> M_ME_TF_1 <37> M_IT_TB_1 <38> M_EP_TD_1 <39> M_EP_TE_1 <40> M_EP_TF_1 <45> C_SC_NA_1 <46> C_DC_NA_1 <47> C_RC_NA_1 <48> C_SE_NA_1 <49> C_SE_NB_1 <50> C_SE_NC_1 <51> C_BO_NA_1 <70> M_EI_NA_1* <100> C_IC_NA_1 <101>...
  • Page 53 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation 8.6 Basic Application Functions Station initialization (station-specific parameter, mark “X” if function is used) Remote initialization Cyclic data transmission (station-specific parameter, mark “X” if function is only used in the standard direction, “R”...
  • Page 54 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Station interrogation (station-specific parameter, mark “X” if function is only used in the standard direction, “R” if only used in the reverse direction, and “B” if used in both directions) global group 1 group 7 group 13 group 2...
  • Page 55 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation Transmission of Integrated totals (station-specific parameter, mark “X” if function is only used in the standard direction, “R” if only used in the reverse direction, and “B” if used in both directions) Mode A: Local freeze with spontaneous Mode B: Local freeze with counter Mode C Freeze and transmit by counter interrogation...
  • Page 56 Section 3 1MAC302441-MB A IEC 60870-5-101/104 protocol implementation File transfer (station-specific parameter, mark “X” if function is used) File transfer in monitor direction Transparent file Transmission of disturbance data of protection Transmission of sequences of events Transmission of sequences of recorded analog values File transfer in control direction Transparent file Background scan...
  • Page 57: Glossary

    Section 4 1MAC302441-MB A Glossary Section 4 Glossary Analog input module ANSI American National Standards Institute Autoreclosing Binary input and output Circuit breaker Cycle building block CBFP Circuit-breaker failure protection CROB Control relay output block Common time of occurrence. The time and date CTO object is an information object that represents the absolute time of day.
  • Page 58 Section 4 1MAC302441-MB A Glossary RER620 Point List Manual...
  • Page 60 Contact us ABB Inc. Distribution Automation 4300 Coral Ridge Drive Coral Springs, FL 33065, USA Phone:+1 (800) 523-2620 Phone:+1 954-752-6700 Fax:+1 954 345-5329 www.abb.com/substationautomation...