Speed Monitoring Relay
Technical Data
Designation
Type
Control voltage (Uc)
Tolerance on Control supply
Frequency
Operating temperature
Sensor Supply
Count inputs
Trip Time delay
Rate Range
Operating modes
Scale factor
Measurement range
Rated output relay current
Relative metering precision
Accuracy of digital display
Pulse duration minimum
Pulse interval minimum
Max. Power consumption
7UG0583-1CU20
7UG0583-1CU20
Speed monitoring relays
110 - 240V AC/DC
0.85x Uc... 1.1x Uc
50/60Hz
0 to 50°C , 95%RH (non-condensing)
12VDC, 30mA (±10%)
(Short circuit protected)
5 to 30VDC from proximity
switches, encoders, solid state devices
or potential free contacts
0 to 99.9 sec (programmable)
Auto ranging resolution
User selectable : RPS / RPM / RPH
Under speed, Over speed and Dual
speed
Programmable from 0.001 to 9.999 x
10
n
where n = -3, -2, -1, 0, 1, 2.
4 - 9999 RPM
5A (AC12)
±15 %
±1 RPM
3 ms
3 ms
3.2 VA
Operating Instructions
Please read and understand these instructions before installing,
operating, or maintaining the equipment.
DANGER
Hazardous voltage can cause death or serious injury.
Disconnect power before working on equipment.
CAUTION
Reliable functioning of the equipment is only ensured
with certified components.
Overvoltage category II
(Refer IEC 60947-1)
NOTICE
This product has been designed for environment A. Use of this product
in environment B may cause unwanted electromagnetic disturbances in
which case the user may require to take adequate mitigation measures.
Terminal connections
WIRING DIAGRAM FOR COUNT INPUT
Encoder
+12V
CNT
GND
COM
-
**
Potential free contacts (NPN)
+12V
CNT
GND
COM
-
Potential free contacts (PNP)
+12V
CNT
GND
COM
-
7UG0
IEC 60947-5-1
NPN
*
NPN
NPN
1