Connecting Cables To Battery Packs For The Ups2000-G-6 Kva/10 Kva - Huawei ESS-240V12-9AhBPVBA Series Quick Installation Manual

Table of Contents

Advertisement

Connecting Cables to Battery Packs for the UPS2000-G-6 kVA/10 kVA

A UPS2000-G-6 kVA/10 kVA requires one battery pack to provide standard backup time, and requires
two to four battery packs to provide long backup time. For a UPS that provides long backup time,
battery packs connect to each other in parallel and then connect to the UPS battery input port. (See
page 5.)
Connecting Cables to Battery Packs for a Single UPS2000-G-6 kVA/10 kVA
For the number of battery packs required by a UPS2000-G-6 kVA/10 kVA that provides standard or
long backup time, see page 5. The following figure shows how to connect a UPS that provides
standard backup time to a battery pack.
Connecting Cables to Battery Packs for a UPS2000-G-6 kVA/10 kVA Parallel System
1. For the number of battery packs required by a UPS2000-G-6 kVA/10 kVA parallel system that
provides standard or long backup time, see page 5. The following figure shows how to connect
each UPS that provides standard backup time in a parallel system to a battery pack.
2. If the number of UPS2000-G-6 kVA/10 kVA parallel system is greater than or equal to 3, each
UPS can be configured with one to four battery packs. The cable connection methods for each
UPS and battery pack in the parallel system are the same as those in a single UPS system.
UPS
BATT.240V DC port
UPS1
BATT.240V DC port
UPS2
BATT.240V DC port
11

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents