OPERATION
SETTINGS
Name/Selection
9802
COMMUNICATION
PROTOCOL SELECTION
9902
APPLIC MACRO
9905
MOTOR NOM VOLT
9906
MOTOR NOM CURR
9907
MOTOR NOM FREQ
9908
MOTOR NOM SPEED
9909
MOTOR NOM POWER
1001* EXT1 COMMANDS
1103* REF1 SEL
1104* REF1 MIN
1105
REF1 MAX
1201* CONST SPEED SEL
1202
CONST SPEED 1
1203
CONST SPEED 2
1204
CONST SPEED 3
1301
MINIMUM AI1
1302
MAXIMUM AI1
1304
MINIMUM AI2
1401
RELAY OUTPUT 1
1501
AO 1 CONTENT SEL
1502
AO 1 CONTENT MIN
1503
AO 1 CONTENT MAX
1504
MINIMUM AO 1
1505
MAXIMUM AO 1
1602* PARAMETER LOCK
1603* PASS CODE
1607* PARAM.SAVE
1608* START ENABLE 1
1611
PARAMETER VIEW
2003* MAX CURRENT
2007* MINIMUM FREQ
2008
MAXIMUM FREQ
2101* START FUNCTION
2102
STOP FUNCTION
12
RENEWAIRE.COM
ABB VFD SUPPLEMENTAL MANUAL
ABB VARIABLE FREQUENCY DRIVES
SUMMARY TABLE OF COMMONLY USED PARAMETERS
NOTE: Parameters not listed in this Table are shipped at ABB's default settings for the HVAC Application Macro.
ABB HVAC Default ACS320/
Settings as Shipped By
ACS355+N831
0=NOT SEL/5=BACnet
0=NOT SEL
HVAC
HVAC
VFD rating
Equal to Motor Voltage
VFD rating
Equal to Motor FLA
60.0 Hz
60.0 Hz
Size Dependent
Set per motor
VFD rating
Equal to Motor HP
1=DI1
1=DI1
1=AI1
0=KEYPAD
0.0 Hz
0.0 Hz
60.0 Hz
60.0 Hz
3=DI3
9=DI3,4
6.0 (Hz)
30.0 Hz
12.0 (Hz)
45.0 Hz
18.0 (Hz)
60.0 Hz
20%
20%
100%
100%
20%/1%
20%
1=READY
2=RUN
103=OUTPUT FREQ
103=OUTPUT FREQ
0.0 Hz
0.0 Hz
60.0 Hz
60.0 Hz
4.0 mA
4.0 mA
20.0 mA
20.0 mA
1=OPEN
0=LOCKED
0
0
0 = DONE
0 = DONE
4=DI4
1=DI1
SHORT VIEW/DEFAULT
LONG VIEW/DEFAULT
Typically set to 125% motor
1.1*I
/1.8*I
2N
2N
FLA **
0.0 Hz
15.0 Hz
60.0 Hz HE units
60.0 Hz
90.0 Hz LE units****
1=AUTO
6=SCAN START
1=COAST
1=COAST
1.800.627.4499
RenewAire
Activates the external serial communication and selects the interface.
Set to 5=BACnet if integrating VFD into BACnet® system.
Pressing SAVE softkey when USER 1 LOAD is selected returns the VFD
to the parameters as shipped from RenewAire. Pressing SAVE softkey
when HVAC DEFAULT is selected returns the VFD to the ABB defaults.
Must be set equal to wired motor voltage.
Must be set equal to motor nameplate FLA. CRITICAL FOR SAFETY.
Must be set 60.0 Hz
Usually 1750.
Must be set to Motor nameplate HP.
Enables 2-wire start-stop when closing contact between 9 & 12.
(Jumper req'd between 10&11.)
Selects signal source for external reference REF 1.
Change to 1=AI1 for operation by an external control signal.
Sets minimum value for speed reference. Used for scaling and
offsetting the input to the VFD output.
Sets maximum value for speed reference. Used for scaling and
offsetting the input to the VFD output.
Enables three-speed operation at three preset speeds using two
switches between 9&13 and 9&14.
Determines preset speed 1.
Determines preset speed 2.
Determines preset speed 3.
Sets minimum value for analog input. Used for scaling and
offsetting the input to the VFD output.
Sets maximum value for analog input. Used for scaling and
offsetting the input to the VFD output.
Sets minimum value for analog input AI2.
Energizes Relay 1 when drive is running.
Terminal 17=COM, 18=N.C., 19= N.O.
Sets the Analog Output of the VFD equal to the Output Frequency
at which it is driving its Motor.
Scales the minimum value of the analog output with respect
to the VFDs Output Frequency.
Scales the maximum value of the analog output with respect
to the VFDs Output Frequency.
Sets the minimum current for the Analog Output.
Sets the maximum current for the Analog Output.
Allows you to lock or change parameters from the keypad.
Entering pass code 358 allows you to change parameter 1602 once.
The entry reverts back to 0 automatically.
Saves parameters to permanent memory
Enables DI1 as the source of the Start Enable Signal.
(SHORT VIEW) Hides less commonly used parameters
CRITICAL PARAMETER. Defi nes motor protection level.
Determines minimum frequency of VFD output
Determines maximum frequency of VFD output
Selects the motor start method. SCAN START provides a
frequency-scanning fl ying start, and corrects backwards rotation.
Sets motor to coast to a halt. Can be set to ramp down to a halt,
following the deceleration time set at 2203.
FUNCTION