38 Technical data

Multiples of frame size R8i

Above values for frame sizes R7/R7i/R8/R8i apply for the multiples of frame size R8i,
except for values of PFH, PFD
PFH
Frame size
(1/h)
T
= 20 a
1
2×R8i
1.74E-09
3×R8i
2.62E-09
4×R8i
3.49E-09
5×R8i
4.36E-09
6×R8i
5.23E-09
7×R8i
6.10E-09
8×R8i
6.97E-09
9×R8i
7.85E-09
10×R8i
8.72E-09
11×R8i
9.59E-09
12×R8i
1.05E-08
The following temperature profile is used in safety value calculations:
670 on/off cycles per year with T = 71.66 °C
1340 on/off cycles per year with T = 61.66 °C
30 on/off cycles per year with T = 10.0 °C
32 °C board temperature at 2.0% of time
60 °C board temperature at 1.5% of time
85 °C board temperature at 2.3% of time.
The STO is a type A safety component as defined in IEC 61508-2.
Relevant failure modes:
The STO trips spuriously (safe failure)
The STO does not activate when requested
A fault exclusion on the failure mode "short circuit on printed circuit board" has been
made (EN 13849-2, table D.5). The analysis is based on an assumption that one
failure occurs at one time. No accumulated failures have been analyzed.
Reaction times are described in section
response times
and MTTF
avg
PFD
PFD
avg
avg
T
= 2 a
T
= 5 a
1
1
1.61E-05
3.90E-05
2.41E-05
5.84E-05
3.21E-05
7.79E-05
4.01E-05
9.74E-05
4.82E-05
1.17E-04
5.62E-05
1.36E-04
6.42E-05
1.56E-04
7.23E-05
1.75E-04
8.03E-05
1.95E-04
8.83E-05
2.14E-04
9.63E-05
2.34E-04
3AXD10000342876 Rev B
on page 14.
. These values are listed below.
D
MTTF
D
(a)
2497
1664
1248
999
832
713
624
555
499
454
416
STO function activation and indication