Hitachi HIDIC EH-150 Applications Manual page 29

Profibus-dp master module
Hide thumbs Also See for HIDIC EH-150:
Table of Contents

Advertisement

6.2.4 Error number
Link module
Link No. 1
Link No. 2
This register can contain two types of errors, Internal errors and External errors, depending on the value of the register
'Error remote address'. If 'Error remote address' is equal to 0xFF this register reports an Internal error otherwise this register
reports an External error.
6.2.4.1 External errors
Value
Description
hex00
Remote node OK
hex03
Function in remote node is not activated.
hex09
No answer data
hex11
No response of the slave
hex12
The master is not into the logical token ring.
6.2.4.2 Internal errors
Value
Description
hex00
No error
hex32-hex35
Internal error
hex36
No database present
hex37
Faulty parameter value in the master parameter.
hex38
No remote node parameter
hex39
Faulty parameter value in the remote node parameter.
hex3A
Double remote node address
hex3B
Projected send process data offset address of a node is
outside the allowable border.
hex3C
Projected receive process data offset address of a node
outside the allowable border.
hex3D
Data areas of remote nodes are overlapping in the
receive process area.
hex3E
Data areas of remote nodes are overlapping in the send
process area.
HexCA
No segment free
hexD4
Faulty reading of configuration data
hexD5
System fault
Others
Not allowed
Table 6.12 Error number
Link address
WRF0E5
WRF145
Table 6.13 External errors
Error source
-
Remote node
Remote node
Remote node
Master
Table 6.14 Internal errors
6-6
Notes
High byte
High byte
Action
-
Check if remote node is Profibus DP
norm conform or the correct GSD files
are used.
Check bus cable
Check bus cable and bus address of the
remote node.
Check FDL/node address of master or
highest station address of other master
systems.
Error source
Action
-
-
Master
Contact supplier
Master
Download database
Project planning
Contact supplier
Project planning
Download database
Project planning
Contact supplier
Project planning
Check remote node addresses.
Project planning
Check projected send offset
addresses.
Project planning
Check projected receive offset
addresses.
Project planning
Check projected receive offset
addresses.
Project planning
Check projected send offset
addresses.
Master
Contact supplier
Master
Download database
Master
Contact supplier
-
Contact supplier
Chapter 6 Indications