3.2.4
Connecting Reset, Pump cleaning
forward and Pump cleaning reverse
terminals to push buttons or PLC
The softstarter has three programmable inputs.
See Figure 9.
In0, has reset event as default
In1, should be changed to Pump cleaning forward,
see chapter 4.4.1 05 Slow speed (pump cleaning
reverse)
2
In2, should be changed to Pump cleaning reverse,
see chapter 4.4.1 05 Slow speed (pump cleaning
reverse)
Internal control voltage - Push buttons
Connect the cables according to Figure 10 to use the
internal control voltage.
Connect the blue reset push button as Reset in
Figure 10
Connect the black pump cleaning toggle right
direction as Forward in
Connect the black pump cleaning toggle left direction
as Reverse in
Figure 10
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
External control voltage - PLC
Connect the cables according to Figure 11 to use an
external control voltage.
Connect PLC control for reset as Reset in Figure 11
Connect PLC control for pump cleaning forward as
Forward in Figure 11
Connect PLC control for pump cleaning reverse as
Reverse in Figure 11
WARNING
Terminal Terminal 13, 14 ,15, 16 and 17 should
be connected using 24V DC only. Other voltages
may damage the softstarter and the warranty may
no longer be valid.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
Connection | Application manual: Waste water pump |
12
Figure 10
K5
K6
Start Stop
In0 In1 In2
GND
K5
K6
Start Stop
In0 In1 In2
GND
9
Figure 9: Terminals 15, 16, 17, 18, 19, 20 and 21
10
L
N
100-250V
50/60 Hz
Figure 10:
Programmable inputs with internal source used.
Typical for push buttons.
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
+24V
4,3 lb.in
11
L
N
100-250V
50/60 Hz
Figure 11:
Programmable inputs with external source used.
Typical for PLC.
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
+24V
4,3 lb.in
1SFC132104M0201
K4
K5
K6
Start Stop In0 In1 In2 DGND
GND
+24V
PSTX
AWG 12 ... 24
2x0,2 .. 1,5 mm
2x0,2 .. 1,5 mm
+
DC
-
K4
K5
K6
Start Stop
In1 In2 DGND
GND
+24V
In0
AWG 12 ... 24
2x0,2 .. 1,5 mm
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2
0,2 .. 2,5 mm
2
2
0,2 .. 2,5 mm
2
2
0,2 .. 2,5 mm
2