ABB PSTX30 Applications Manual page 13

Waste water pump
Table of Contents

Advertisement

3.2.5
Connecting line contactor and
Run pilot light
The output relay gives a signal depending on the selected
function.
K4 is set to Run by default.
Connect the cables for controlling the line contactor to
terminal 4 and 5 for NO control of the contactor.
See Figure 12.
Connect the green Run pilot light parallel to the supply
voltage for the line contactor, e.g. by using an auxiliary
contact block to the line contactor.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
3.2.6
Connecting Event pilot light
The output relay gives a signal depending on the selected
function.
K6 is set to Event by default.
Connect the cables for the yellow Fault and Protection
pilot light to terminal 10 and 11 for NO control of the pilot
light. See Figure 13.
Tightening torques and cable dimensions.
L
N
100-250V
50/60 Hz
K4
K5
3.2.7
Extension I/O for extra inputs and
outputs (optional)
If more inputs and outputs are needed, connect
accessory DX111-FBP.0 (1SAJ611000R0101) from ABB.
This will give additional:
8 digital input
4 ouput relay
1 analog output
The cables shall be connected to terminals 23, 24, 28
and 30. See Figure 14.
Tightening torques and cable dimensions.
Com 3
Temp In
+(B) -(A)
T1 T2 T3
23 24
25 26 27
K6
Start Stop In0 In1 In2
GND
+24V
K6
Start Stop In0 In1 In2
GND +24V
Analog out
+24V
+ GND
28
29 30
1SFC132104M0201
12
Figure 12:
Programmable output relay K4, terminals 4, 5 and 6
M3,5
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
13
Figure 13:
Programmable output relay K6, terminals 10, 11 and 12
M3
3,5 x 0,6 mm
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
14
Figure 14: Extension I/O
3,5 x 0,6 mm
M3
(0.138 x 0.024 in)
0,5 Nm
4,3 lb.in
| Application manual: Waste water pump | Connection
2
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
Com 3
Temp In
Analog out
+(B) -(A)
T1 T2 T3
+24V + GND
23 24 25 26 27
28 29 30
A
AWG 12 ... 24
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
2
0,2 .. 2,5 mm
2
2x0,2 .. 1,5 mm
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pstx370

Table of Contents