5. SPECIFICATIONS OF ELECTRICAL PARTS
No.
Parts name
1
Compressor
2
Fan motor
3
4-way valve coil
4
PMV coil
5
High-pressure SW
6
Reactor
7
P.C. board
8
Fuse (Mounted on P.C. board)
9
Fuse
10
Fuse (Mounted on P.C. board)
11
Outdoor temp. sensor (TO sensor)
12
Heat exchanger temp. sensor (TE sensor)
13
Suction temp. sensor (TS sensor)
14
Discharge temp. sensor (TD sensor)
15
Heat exchanger temp. sensor (TL sensor)
16
Compressor thermo. (Protection)
Type
DX380A2T-20M
ICF-280-A100-1
DXQ-1490
CAM-MD12TF-18
ACB-4UB166W
CH-57-Z-T;R
MCC-1758
-
-
-
-
-
-
-
-
CS-12AL
- 26 -
Specification
3 phase, 4P, 3750W
Output 100 W
-
-
OFF:4.15MPa
8.88~10.01mH, 16A
-
AC250 V, 50 A
AC250 V, 10 A
AC250 V, 3.15 A
10 kΩ at 25°C
10 kΩ at 25°C
10 kΩ at 25°C
50 kΩ at 25°C
50 kΩ at 25°C
OFF: 125 ± 4°C, ON: 90 ± 5°C