Chapter 1 Part Names - Mitsubishi Electric MELSEC iQ-R Series User Manual

Cc-link ie tsn
Hide thumbs Also See for MELSEC iQ-R Series:
Table of Contents

Advertisement

1
PART NAMES
This chapter describes the names of each part of the RJ71GN11-T2.
(1)
(2)
(3)
(4)
(5)
No.
Name
(1)
RUN LED
*1
ERR LED
MST LED
*1
D LINK LED
P1 SD/RD LED
P2 SD/RD LED
(2)
Dot matrix LED
(3)
P1
*1
L ER LED
LINK LED
1 PART NAMES
16
Description
Indicates the operating status.
On: Normal operation
Off: Error ( MELSEC iQ-R CC-Link IE TSN User's Manual (Application))
Indicates the error status of the module. ( MELSEC iQ-R CC-Link IE TSN User's Manual (Application))
On: Error or error detection on all stations
Flashing (500ms interval): Data link faulty station detection
• Unicast mode: Flashing only at the master station
• Multicast mode: Flashing at the master station and local station. However, the LED does not flash at the local station if a data
link error occurs at the authentication Class A remote station during data link. (The LED remains off.)
Flashing (200ms interval): Error
Off: Normal operation
Indicates the operating status.
On: Operating as a master station
Off: Operating as a local station
Indicates the cyclic transmission status.
On: Cyclic transmission being performed
Flashing: Cyclic transmission stopped
Off: Disconnected
Indicates the data sending/receiving status.
On: Data being sent or received
Off: Data not sent nor received
Displays the station number set for the module.
Station number or parameter not set: "  "
Master station: 0
Local station: 1 to 120
■At error
All lights turn off. However, some errors do not cause all lights to turn off. Check the RUN LED and ERR LED to see if an error
has occurred.
■In module communication test mode
Displays the module communication test result. ( MELSEC iQ-R CC-Link IE TSN User's Manual (Application))
■In offline mode
Displays "".
■When the module status setting is "Empty"
Displays "  "
Port for CC-Link IE TSN connection. Connect an Ethernet cable.
For wiring methods and wiring precautions, refer to the following.
( Page 56 WIRING)
Indicates the port status.
On: Abnormal data received or loopback being performed
Off: Normal data received and loopback not performed
Indicates the link status.
On: Link-up
Off: Link-down