Advertisement

Quick Links

ABB DRIVES FOR WATER
ACQ580-31 drives
US Quick installation guide

Advertisement

Table of Contents
loading

Summary of Contents for ABB ACQ580-31

  • Page 1 — ABB DRIVES FOR WATER ACQ580-31 drives US Quick installation guide...
  • Page 2: List Of Related Manuals In English

    For manuals not Document library on the Internet available in the Document library, contact your local ABB representative. The code below opens an online listing of the manuals applicable to this product. ACQ580-31 manuals...
  • Page 3: Obey The Safety Instructions

    EN – US quick installation guide This guide briefly describes how to install the drive. For complete information on installation, see ACQ580-31 drives hardware manual (3AXD50000045935 [English]). For cabinet installation, see also ACS580, ACH580 and ACQ580 drive module frames R3, R5 to R9 for cabinet installation (options +P940 and +P944) supplement (3AXD50000210305 [English]).
  • Page 4: Iec Ratings

    … For information on reforming the capacitors, see Converter module capacitor reforming instructions (3BFE64059629 [English]), available on the Internet at abb.com/drives/documents. Data IEC ratings  ACQ580-31- Cu cable (AWG/kcmil) UL fuse Losses (W) 3-phase U = 480 V 09A5-4 JJS-15...
  • Page 5: Select The Power Cables

    EN – US quick installation guide 5 Select the power cables See the table on page 4. Data Ensure cooling See the table on page 4. No condensation or frost is allowed. The allowed Data operating temperature range of the drive without derating is -15 to +40 °C. Protect the drive and input power cable with correct fusing Check on the fuse time-current curve to ensure that the operating time of the fuse is below 0.5 seconds for frames R3 and R6 and below 0.1 seconds for frame R8.
  • Page 6: D - Check The Insulation Of The Power Cables And The Motor

    6 EN – US quick installation guide D – Check the insulation of the power cables and the motor Check the insulation of motor and motor cable. See figure on page 12. Note: Moisture inside the motor casing will reduce the insulation resistance. If moisture is suspected, dry the motor and repeat the measurement.
  • Page 7: G - Connect The Control Cables

    EN – US quick installation guide 7 G – Connect the control cables Procedure: 1. Remove the front cover(s) if not already removed. 2. Frame R3: Lift the control panel holder up. See figure on page 13. G (R3)… 3. Remove the rubber grommets from the bottom plate for the cable conduits to be installed.
  • Page 8: Default Io Connection Diagram

    8 EN – US quick installation guide Default IO connection diagram  Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND Analog input circuit common +10V Reference voltage 10 V DC Actual feedback: 0…10 V AGND Analog input circuit common...
  • Page 9 Code. For installation in the United States, obey any other applicable local codes. For installation in Canada, obey any applicable provincial codes. • Note: Circuit breakers must not be used without fuses in the USA. Consult ABB for suitable circuit breakers.
  • Page 10 10 EN – US quick installation guide or electric shock, current-carrying parts and other components of the device should be examined and replaced if damaged. • The drive provides motor overload protection. For the adjustments, see the firmware manual. • For the drive overvoltage category and pollution degree, see the hardware manual.
  • Page 11 Figures USA B (R3) …B (R6, R8) UL Type 12 UL Type 1 UL Type 12) ×4 R3: M5 (#10) R6, R8 R6: M8 (5/16″) R8: M8 (5/16″) >61.0 >134.51 B (R6, R8)… A (R6, R8) Corner-grounded delta system UL Type 1 UL Type 12 TN-S system IT system...
  • Page 12 …F (R8)… …F… R6…R8 U1-V1, U1-W1, V1-W1 U1-PE, V1-PE, W1-PE 1000 V DC, > 100 Mohm …F… Drive UDC+ UDC- T1/U T2/V T3/W … … 3 ~ M (PE) (PE) F (R6)… …F (R6, R8)… …F (R3)… 1.7 N·m (1.2 lbf·ft) L1, L2, L3, T1/U, T2/V, T3/W: 1.7 N·m (1.2 lbf·ft)
  • Page 13 …F (R6)… …F (R6, R8)… …G (R3)… 2.9 N·m (2.1 lbf·ft) 0.5…0.6 N·m (0.4 lbf·ft) L1, L2, L3, T1/U, T2/V, T3/W: 5.6 N·m (4.1 lbf·ft) …F (R8)… 9.8 N·m (7.2 lbf·ft) L1, L2, L3, T1/U, T2/V, T3/W: 30 N·m (22.5 lbf·ft) G (R3)…...
  • Page 14 …G (R6)… …G (R8)… …G Reference voltage and analog inputs and outputs Signal cable shield (screen) Output frequency/speed reference: 0…10 V 1…10 kohm AGND Analog input circuit common 0.5…0.6 N·m (0.4 lbf·ft) +10V Reference voltage 10 V DC Actual feedback: 0…10 V 0.5…0.6 N·m (0.4 lbf·ft) AGND Analog input circuit common...
  • Page 15 H (R3, R6, R8)... …H (R8) R8 UL Type 12 R3 UL Type 1 R3 UL Type 12 2 N·m (1.5 lbf·ft) 2 N·m (1.5 lbf·ft) R6 UL Type 1 R6 UL Type 12 2 N·m (1.5 lbf·ft)
  • Page 17 — ABB DRIVES FOR WATER Quick start-up guide Basic ACQ580 program setup...
  • Page 18 [Page intentionally left blank] Rev 2016-02-17...
  • Page 19: Quick Start-Up Guide

    Quick start-up guide This guide describes how to start-up the drive using the First start assistant on the Hand-Off-Auto control panel. For complete information on start-up, see ACQ580 firmware manual (3AXD50000035867 [English]). Before you start Ensure that the drive has been installed as described in chapter R1…R4 Quick on page or in chapter...
  • Page 20 The First start assistant guides you through the first start-up. The assistant begins automatically. Wait until the control panel enters the view shown on the right. Select the language you want to use by highlighting it (if not already highlighted) and pressing (OK).
  • Page 21 Refer to the motor or pump nameplate for the following nominal value settings of the motor. Enter the values exactly as shown on the motor or pump nameplate. Example of a nameplate of an induction (asynchronous) motor: ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.
  • Page 22 If you want to make a backup of the settings made so far, select Backup and press (Next). If you do not want to make a backup, select Not now and press (Next). The first start is now complete and the drive is ready for use.
  • Page 23 3 – Hand/Off/Auto operation The drive can be in remote control or local control, and in local control there are additionally two different modes. Remote control: Drive is controlled from the I/O or the fieldbus. • Top row of the view shows Auto. Local control: Drive is controlled from the control panel.
  • Page 27: Further Information

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type designation and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/searchchannels.
  • Page 28 © Copyright 2019 ABB. All rights reserved. Specifications subject to change without notice.

Table of Contents