ABB ACS 600 Supplement To Firmware Manual page 11

Standard application program 5.0; master/follower application macro
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

Follower Fault
Information Wiring
X22
1 2 3 4 5 6 7 8 9
X2 18 19 20
Figure 2-3 Follower fault information wiring. Note that the external input/output signals of ACS 601 and
ACS 604 units connect directly to the NIOC board I/O terminal blocks. On ACS 607, the I/O terminals
of the NIOC board are optionally wired to a separate terminal block (X2) at the factory.
ACS 600 Master/Follower Application Macro
The Follower does not send any feedback data via the serial Master/
Follower Link. Therefore it is highly recommended to separately wire
the Follower fault information back to the Master. The connection stops
both the Master drive and the Follower drives upon a Follower fault.
ACS 601, ACS 604, ACS 607 without Terminal Block X2
Master
ACS 60x
X27
1 2 3
X22
1 2 3 4 5 6 7 8 9
ACS 607 with Terminal Block X2 (Optional)
Master
ACS 60x
30 31 32
X2 18 19 20
Chapter 2 – Installation and M/F Link Specification
Follower
ACS 60x
X27
1 2 3
X22
1 2 3 4 5 6 7 8 9
Follower
ACS 60x
30 31 32
X2 18 19 20
Follower
ACS 60x
X27
1 2 3
Follower
ACS 60x
30 31 32
2-3