External Control Connections - ABB ACS 600 Supplement To Firmware Manual

Standard application program 5.0; master/follower application macro
Hide thumbs Also See for ACS 600:
Table of Contents

Advertisement

Chapter 2 – Installation and M/F Link Specification
External Control
Connections
1)
Changes external speed reference source. In most
cases this is not required (can be left unconnected).
2)
Open switch = Constant speed is not activated.
Closed switch = Constant speed defined with Parameter
12.05 replaces the external speed reference.
3)
Changes the speed acceleration/deceleration ramp.
Note: Does not change the Follower ramp. In most
cases should be left unconnected.
4)
See Follower fault information wiring. Note that the
external input/output signals of ACS 601 and ACS 604
units connect directly to the NIOC board I/O terminal
blocks. On ACS 607, the I/O terminals of the NIOC
board are optionally wired to a separate terminal block
Figure 2-2 External control connections for the Master station. The markings of the NIOC board
terminals are given above. Note that the external input/output signals of ACS 601 and ACS 604 units
connect directly to the NIOC board I/O terminal blocks. On ACS 607, the I/O terminals of the NIOC
board are optionally wired to a separate terminal block (X2) at the factory. See the ACS 604/607
Installation and Start-up Manual for the corresponding terminal markings.
2-2
The default parameter settings of the Master/Follower macro define the
control connections according to the circuit diagram below.
rpm
A
Ready
Running
No Fault
Function
Terminal Block X21
1
VREF
Reference voltage 10 VDC
max. 10 mA
2
GND
3
AI1+
External reference 1 (Speed reference)
0 ... 10 V
4
AI1-
5
AI2+
External reference 2
0 ... 20 mA
6
AI2-
7
AI3+
Not specified in this application
0 ... 20 mA
8
AI3-
9
AO1+
Speed
0 ... 20 mA <–> 0 ... Motor nom. speed
10
AO1-
11
AO2+
Current
0 ... 20 mA <-> 0 ... Motor nom. current
12
AO2-
Terminal Block X22
1
DI1
STOP/START
2
DI2
FORWARD/REVERSE
3
DI3
EXT1/EXT2 SELECT
4
DI4
CONST SPEED SEL
5
DI5
ACCEL/DECEL 1/2 SEL
6
DI6
RUN ENABLE
7
+24 DVDC
+24 VDC max. 100 mA
8
+24 DVDC
9
Digital ground
DGND
Terminal Block X23
1
+24 VDC
Auxiliary voltage output 24 VDC
max. 250 mA
2
GND
Terminal Block X25
1
RO11
Relay output 1
2
RO12
READY
3
RO13
Terminal Block X26
1
RO21
Relay output 2
2
RO22
RUNNING
3
RO23
Terminal Block X27
1
RO31
Relay output 3
2
RO32
FAULT (–1)
3
RO33
ACS 600 Master/Follower Application Macro