Check first when you have a trouble

6.5
Check first when you have a trouble
POINT
If the cause is still unknown after every check, it is recommended to initialize the parameters (initial value) then
set the required parameter values and check again.
6.5.1

Motor does not start

Check
points
Appropriate power supply voltage is not applied.
(Operation panel display is not provided.)
Main
Circuit
Motor is not connected properly.
The jumper across P/+ and P1 is disconnected.
Start signal is not input.
Both the forward and reverse rotation start signals (STF,
STR) are input simultaneously.
Frequency command is zero.
(RUN LED on the operation panel is flickering.)
Input
Output stop signal (MRS) or error reset is ON.
Signal
(RUN LED on the operation panel flickers while MRS
signal or error reset is ON.)
Shorting wires across S1 and PC and across S2 and
PC are disconnected even though the safety stop
function is not being used.
was pressed.
(Operation panel indication is
The setting value "1" is set in the X12 signal (Bit11),
which gives a control input command through FL remote
communication.
Pr. 0 Torque boost setting is improper when V/F control is
used.
Pr. 78 Reverse rotation prevention selection is set.
Parameter
Pr. 13 Starting frequency setting is greater than the
Setting
running frequency.
Frequency settings of various running frequency (such
as multi-speed operation) are zero.
Especially, Pr. 1 Maximum frequency is zero.
Pr. 15 Jog frequency setting is lower than the Pr. 13
Starting frequency setting during the JOG operation.
204
Possible Cause
(PS).)
Countermeasures
Power ON a moulded case circuit breaker (MCCB), an
earth leakage circuit breaker (ELB), or a magnetic
contactor (MC).
Check for the decreased input voltage, input phase loss,
and wiring.
Check the wiring between the inverter and the motor.
Securely fit a jumper across P/+ and P1.
When using a DC reactor (FR-HEL), remove the jumper
across P/+ and P1, and then connect the DC reactor.
Check the start command source, and input a start
signal.
PU operation mode:
Network operation mode: STF/STR signal
Turn ON only one of the forward and reverse rotation
start signals (STF or STR).
If STF and STR signals are turned ON simultaneously in
the initial setting, a stop command is given.
Enter a frequency command.
Turn MRS signal or error reset OFF.
Inverter starts the operation with a given start command
and a frequency command after turning OFF MRS
signal or error reset.
Before turning OFF, ensure the safety.
When not using the safety stop function, short across
terminals S1 and PC and across S2 and PC with
shorting wire.
During the Network operation mode, check the method
of restarting from a
input stop from the operation
panel.
Set "0" in the X12 signal (Bit11), which gives a control
input command through FL remote communication.
Increase Pr. 0 setting by 0.5% increments while
observing the rotation of a motor.
If that makes no difference, decrease the setting.
Check the Pr. 78 setting.
Set Pr. 78 when you want to limit the motor rotation to
only one direction.
Set running frequency higher than Pr. 13.
The inverter does not start if the frequency setting signal
is less than the value set in Pr. 13.
Set the frequency command according to the
application.
Set Pr. 1 higher than the actual frequency used.
Set Pr. 15 Jog frequency higher than Pr. 13 Starting
frequency.
Refer
to
page
15
28
57, 74
20
58
57
24
195
57
94
167
119
105
171