Connection method
(1) Reserved connector
(2) Rigid pipe connector
(3) Rigid pipe
Connecting the Humidifier Water Inlet Hose
4.3
A humidifier water inlet hose is delivered with the equipment
and is pulled the hose along the reserved pipe clamp on the
cabinet side to the top of the cabinet.
1. Pull the hose to the top of the cabinet and route the hose
through the humidifier water inlet hose hole.
2. Connect the water inlet hose of the smart cooling product
to the engineering pipe.
4.4
Connecting the Chilled Water Inlet and Outlet Pipes
1. Wrap thermal insulation foam around the whole pipes after pipes are connected.
2. Due to the hardening property of yellow adhesive, nitrogen injection and pressure preserve
should be operated 8 hours after the adapter is connected.