Installation Verification; Equipment Power-On - Huawei FusionCol8000-C210 Quick Manual

In-room chilled water smart cooling product
Hide thumbs Also See for FusionCol8000-C210:

Advertisement

(Optional) Connecting the Motorized Damper
5.7
For details about how to connect the motorized damper, see the documents delivered with it.
6

Installation Verification

Check Item
Expected Result
The cabinet is installed properly without any tilt. The cabinet is
Cabinet
secured to the base by using bolts. The foreign matter inside
the cabinet, such as cable ties and stubs, has been cleaned up.
Fan
The fan has no foreign matter inside.
The foreign matter inside the water pan is cleaned up.
Water pan
Differential
The cable ties are securely tightened around pressure tubes.
pressure
There is no foreign matter in pressure tubes. The pressure
switch
tubes show no obvious bends.
Exhaust
The exhaust valve is closed.
valve
Drainage
The drainage valve is closed.
valve
The air filter is correctly installed according to the airflow
Air filter
direction marked on the frame.
The chilled water valve and its actuator are securely installed.
The chilled water connector joints have been wrapped with
thermal insulation foam, and no metal or hose are exposed.
Chilled water
Cables are securely connected to the chilled water valve and its
valve
actuator. Cables to the chilled water valve and its actuator are
secured. Check that the manual button on the actuator is reset
(the button bounces up).
7

Equipment Power-On

7.1
Power-On
1. Users are classified into admin and operator users, and admin users have more rights than
operator users. The preset password is 000001 for both types of users. For system security
purposes, change the preset password upon first login.
2. A login session automatically expires if no operation is performed in three minutes. It is
recommended that you tap
are complete.
1. Turn on the general switch, fan switch QF3, QF4, QF5, QF6, electric heater switch QF7 (apply to
model with heating). For a device that has two power inputs, turn on the active power switch
QF1 and standby power switch QF2.
2. Powered on the cabinet.
Select the language: English or Chinese.
Select the date & time settings: date format, date, time, and time zone.
On the home screen, tap Settings > System Settings > T/H Sensor to change temperature
and humidity control types or set points.
at the lower right corner to manually log out after operations
13
Actual Result
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed
□Passed □Failed