Siemens SIMATIC S7-1500 Manual page 13

Digital output module
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Wiring
3.2 Terminal assignment X10 and X11.
Terminal and address assignment
For connecting actuators, we recommend using the SIMATIC TOP connect pre-assembled
connecting cables and SIMATIC TOP connect connection modules. However, if you choose
another wiring option, you will need the following tables.
Table 3- 1
Terminal
12
Assignment for connector X10 of the module
Channel
40
2L+
38
2M
36
Channel 31
34
Channel 30
32
Channel 29
30
Channel 28
28
Channel 27
26
Channel 26
24
Channel 25
22
Channel 24
20
2L+
18
2M
16
Channel 23
14
Channel 22
12
Channel 21
10
Channel 20
8
Channel 19
6
Channel 18
4
Channel 17
2
Channel 16
Assignment for outputs to X10
Address
Terminal
39
---
---
37
35
x+3.7
33
x+3.6
x+3.5
31
29
x+3.4
27
x+3.3
x+3.2
25
23
x+3.1
x+3.0
21
19
---
17
---
x+2.7
15
x+2.6
13
11
x+2.5
x+2.4
9
7
x+2.3
5
x+2.2
x+2.1
3
1
x+2.0
Digital output module DQ 64x24VDC/0.3A BA (6ES7522-1BP00-0AA0)
Channel
1L+
1M
Channel 15
Channel 14
Channel 13
Channel 12
Channel 11
Channel 10
Channel 9
Channel 8
1L+
1M
Channel 7
Channel 6
Channel 5
Channel 4
Channel 3
Channel 2
Channel 1
Channel 0
Equipment Manual, 07/2020, A5E48024569-AA
Address
---
---
x+1.7
x+1.6
x+1.5
x+1.4
x+1.3
x+1.2
x+1.1
x+1.0
---
---
x.7
x.6
x.5
x.4
x.3
x.2
x.1
x.0

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simatic et 200mp6es7522-1bp00-0aa0

Table of Contents