Loading I&M data
Which I&M data can you load into the IO controller and its IO devices?
You can load the I&M 1 data (plant designation and location identifier) and/or the I&M 2 data
(installation date) and/or the I&M 3 data (additional information) into the real hardware.
Requirement
● The option "Download I&M data" is enabled in the project settings ("Extras" > "Settings",
"Hardware configuration" > "Compile & download").
● There is an online connection to the IO controller and its IO devices to which you want to
load I&M data.
● You have entered the I&M data to be loaded in the properties of the affected IO controller
and its IO devices (Inspector window: "Properties" tab > "General" tab > "Identification &
Maintenance").
Downloading the configuration
For technical reasons, loading the configuration with I&M data for the IO controller and its IO
devices must take place in the following two steps:
● First, the plant is configured and the configuration data is loaded onto the IO controller.
Only the "Device configuration" is loaded into the IO controller in the "Load preview"
dialog. This means that you enable the "Load data" option in the drop-down list for
"Device configuration". The plant does not need to be fully set up. The I&M data is not
loaded in the first step. In this step, loading I&M data is disabled in the "Load preview"
dialog, i.e. the option "Load nothing" is disabled (default setting).
● The plant is commissioned in the second step (set IO controller to the "OPERATE" state
and connect CP 1626). You can still complete or update the I&M data and you perform
the "Load data" option again for the IO devices after you have disabled all other options in
this dialog.
CP 1626
Operating Instructions, 11/2018, C79000-G8976-C434-03
Configuration
3.1 Loading I&M data
23