Frame Size, Standards, &
Installation

Frame Sizes

Available frame sizes are 80 through 225
Totally Enclosed Fan Cooled (TEFC).
The EQP Global IEC Series Low-Voltage
50/60 Hz Metric Motor is manufactured in
accordance with standard IEC/EN 60072
dimensions.
The EQP Global IEC Series Low-Voltage 50/
60 Hz Metric Motor will be CE marked. Marking
indicates compliance with the relevant EU
Directives. A Declaration of Conformity shall
accompany the product, where applicable. In
the event that any documentation is found to
be missing, please contact the
Support Center
for assistance.
EQP Global IEC Series motors in frames 80 –
132 are dual voltage and designed for both
Wye and Delta connections. Refer to the
connection diagram received with the unit.
EQP Global IEC Series motors are
manufactured with the terminal box mounted to
the top of the motor.
The motor uses the standard connection
configuration and, while facing the drive end of
the motor, the standard rotation is clockwise
(CW). EQP Global IEC Series motors are bi-
directional.

Declaration of Conformity

EQP Global IEC Series motors will, at a
minimum, meet the Low Voltage Directive
(2014/30/EU). Other Directives may also apply
based on the product scope.

Declaration of Incorporation

Final conformity to the Machinery Directive 2006/
42/EC has to be established by the installer or
commissioning party once incorporated into the
final application.

Electromagnetic Compatibility

Installation of the Toshiba EQP Global IEC
Series Low-Voltage 50/60 Hz Metric Motor
shall be performed as described in this manual
to ensure compliance with the EMC Directive.
In the case of an installation or application in
www.toshiba.com/tic/
Motor Size, Compliance, & Installation
EQP Global IEC Series Low-Voltage 50/60 Hz Metric Motor
which an ASD, soft starter, or electronic control
is being used, the installer/system integrator or
commissioning party will be required to verify
that the system/application meets the EMC
Directives.
When used in accordance with the directive
and operated in an electrical supply system as
characterized by EN 50160, the EQP Global
IEC Series Low-Voltage 50/60 Hz Metric Motor
complies with the requirements of the EC
Directive concerning electromagnetic
compatibility 2014/30/EU.
• Motor protection from overloads, peak starting
currents, short circuit current, and ground fault
currents, should be in strict accordance with the
TIC Customer
IEC, local electrical codes, and building codes.
• Avoid touching the hot surfaces of the electric
motor without wearing the proper protection.
• Keep the terminal box cover in place and
secured while the motor circuits are powered.
• Personal hearing protection is required when
exposed to noise levels exceeding 70 dBA.
• Only
maintenance.
• To reduce the risk of fire or explosion, do not
install Toshiba EQP Global IEC Series Metric
motors in hazardous environments. EQP
Global IEC Series Metric motors are not
certified for Zone 1 or 2 applications.
• Do not disable or bypass any safety guards or
protective devices.
• Proper circuit protection is required to prevent
automatic reset devices from automatically
restarting the motor.
Note:
CAUTION
CAUTION
WARNING
Qualified Personnel
are to perform
DANGER
The equivalent lead wire markings per
IEC are: TI (U1), T2 (V1), T3 (W1),
T4 (U2), T5 (V2), T6 (W2), T7 (U5),
T8 (V5), T9 (W5), T10 (U6) T11 (V6),
T12 (W6).