1. Model Selecting and Capacity Calculator
1-6. Straight Equivalent Length of Joints
Design the tubing system by referring to the following table for the straight equivalent length of joints.
Table 2-8 Straight Equivalent Length of Joints
Gas tubing size (in.(mm))
90° elbow
45° elbow
U-shape tube bent
(R2–23/64–3–15/16 in.)
T r ap bend
Y-branch distr ibution joint
Ball v alve f or ser vice
1/2"
5/8"
3/4"
7/8"
(12.7)
(15.88)
(19.05)
(22.22)
1
1.1
1.4
1.6
0.8
0.9
1
1.2
3
3.4
4.1
4.7
7.5
9.2
10.5
12.5
Equivalent length conversion not needed.
Equivalent length conversion not needed.
2 - 9
Design of 3WAY VRF SYSTEM
Unit: ft.
1"
1-1/8"
1-3/8"
(25.4)
(28.58)
(38.1)
1.7
1.9
2.5
1.3
1.4
1.8
5.1
5.6
7.4
14.1
15.4
19.2
1
2
3
4
5
6
7
8