Appendix D - Connections For Configuring And Testing The Modbus Card - ABB Zenith 50P-2035 Operation And Maintenance Manual

Modbus network card for mx150/mx250 (mx version 6.0+ only)
Table of Contents

Advertisement

MODBUS NETWORK CARD DEFAULT SETTINGS
SLAVE ADDRESS 1
RTU MODE
8 DATA BITS, 9600 BAUD, NO PARITY, 2 STOP BITS.
PS-5140
NETWORK PLUG
CONNECTOR
VERIFY POLARITY
CONNECTIONS
A
B
SEE NOTE 1
SEE NOTE 6
ADDRESS/STATUS INDICATOR LEDs
(REF . PG.1, FIG. 2)
NOTES:
1.
USE TWISTED PAIR CABLE (BELDEN 8471, 16 AWG) (ABB ZENITH
PART # WMW-453).
2.
CONFIGURATION JUMPER (J4) MUST BE INSTALLED TO CHANGE MODBUS
ADDRESS AND MODE. REMOVE FOR NORMAL OPERATION.
3.
MODBUS NETWORK CARD ASSEMBLY MUST BE INSTALLED ON THE CON-
TROLLER. REFER TO APPENDIX F .
50W-1208
4.
USE SOFTWARE PROGRAMMING PACKAGE 50P-1111. REFER TO PAGE #
RS232/485
"CONFIGURING A MODBUS NETWORK CARD. "
CONVERTER
5.
TO TEST THE MODBUS NETWORK, REFER TO PAGE # "TESTING A MODBUS
NETWORK" PROCEDURE.
6.
CONNECT TO THE SERIAL PORT OF THE PC WHICH HAS THE 50P-1111
SOFTWARE PACKAGE.
50P-2035
MODBUS
NETWORK CARD
ASSEMBLY
CONFIGURATION JUMPER (J4)
(NOTE 2)