Cabinet No. Circuit Breaker Category
Transformer
LA11
ACB
incoming
LA11
Bus tie
ACB
LA13
UPS main input
ACB
LA13
UPS bypass input
ACB
UPS maintenance
LA14
ACB
bypass
LA14
UPS output
ACB
ACB Parameter Settings
Current
Parameter
Level
Overload Protection: L (Touch screen setting)
Time-delayed overcurrent protection: S (Touch screen setting)
3200A
Instantaneous overcurrent protection: I (Touch screen setting)
Earth fault protection: G (Touch screen setting)
Overload Protection: L (Touch screen setting)
2500A
Time-delayed overcurrent protection: S (Touch screen setting)
Instantaneous overcurrent protection: I (Touch screen setting)
Overload Protection: L (Touch screen setting)
3200A
Time-delayed overcurrent protection: S (Touch screen setting)
Instantaneous overcurrent protection: I (Touch screen setting)
Overload Protection: L (Touch screen setting)
3200A
Time-delayed overcurrent protection: S (Touch screen setting)
Instantaneous overcurrent protection: I (Touch screen setting)
Overload Protection: L (Touch screen setting)
3200A
Time-delayed overcurrent protection: S (Touch screen setting)
Instantaneous overcurrent protection: I (Touch screen setting)
Overload Protection: L (Touch screen setting)
3200A
Time-delayed overcurrent protection: S (Touch screen setting)
Instantaneous overcurrent protection: I (Touch screen setting)
Trip Threshold
Trip Time
l1=0.4–1.0*ln
t1=3–144S
Threshold step: 0.01*ln
Time Step: 3S (3*l1)
l2=0.6–10*ln
t2=0.05–0.8S
Threshold step: 0.1*ln
Time Step: 0.01S
l3=1.5–15*ln
Instantaneous
Threshold step: 0.1*ln
l4=0.2–10*ln
t4=0.1–1.0S
Threshold step: 0.02*ln
Time Step: 0.05S
l1=0.4–1.0*ln
t1=3–144S
Threshold step: 0.01*ln
Time Step: 3S (3*l1)
l2=0.6–10*ln
t2=0.05–0.8S
Threshold step: 0.1*ln
Time Step: 0.01S
l3=1.5–15*ln
Instantaneous
Threshold step: 0.1*ln
l1=0.4–1.0*ln
t1=3–144S
Threshold step: 0.01*ln
Time Step: 3S (3*l1)
l2=0.6–10*ln
t2=0.05–0.8S
Threshold step: 0.1*ln
Time Step: 0.01S
l3=1.5–15*ln
Instantaneous
Threshold step: 0.1*ln
l1=0.4–1.0*ln
t1=3–144S
Threshold step: 0.01*ln
Time Step: 3S (3*l1)
l2=0.6–10*ln
t2=0.05–0.8S
Threshold step: 0.1*ln
Time Step: 0.01S
l3=1.5–15*ln
Instantaneous
Threshold step: 0.1*ln
l1=0.4–1.0*ln
t1=3–144S
Threshold step: 0.01*ln
Time Step: 3S (3*l1)
l2=0.6–10*ln
t2=0.05–0.8S
Threshold step: 0.1*ln
Time Step: 0.01S
l3=1.5–15*ln
Instantaneous
Threshold step: 0.1*ln
l1=0.4–1.0*ln
t1=3–144S
Threshold step: 0.01*ln
Time Step: 3S (3*l1)
l2=0.6–10*ln
t2=0.05–0.8S
Threshold step: 0.1*ln
Time Step: 0.01S
l3=1.5–15*ln
Instantaneous
Threshold step: 0.1*ln
Setting
lr1=1.0*ln=3200A
t1=96s (3*lr1)
Ir2=10xln=32000A
t2=0.8s
Ir3=15xln=48000A
Ir4=0.4xln=1280A
Ir1=1.0xln=2500A
t1=69s (3*lr1)
Ir2=9.4xln=23500A
t2=0.4s
Ir3=15xln=37500A
Ir1=1.0xln=3200A
t1=18s (3*lr1)
Ir2=5.4xln=17280A
t2=0.24s
Ir3=15xln=48000A
Ir1=1.0xln=3200A
t1=18s (3*lr1)
Ir2=5.4xln=17280A
t2=0.24s
Ir3=15xln=48000A
Ir1=1.0xln=3200A
t1=6s (3*lr1)
Ir2=3.9xln=12480A
t2=0.14s
Ir3=15xln=48000A
Ir1=1.0xln=3200A
t1=3s (3*lr1)
Ir2=2.7xln=8640A
t2=0.08s
Ir3=15xln=48000A