Line Lengths And Cross-Sections; Connecting 24 V Dc; Connecting The Digital 24 V Inputs Sel And Mod - Bosch rexroth IndraControl VAC 08.1 Operating Instructions Manual

Table of Contents

Advertisement

18/33
Mounting, demounting and electric installation

10.5.2 Line lengths and cross-sections

Connection
24 V +
24 V -
SEL +
MOD +
SEL/MOD -
Functional earth
Tab. 10-1: Cable lengths and cross-sections for the plugs X1S1
NOTICE
Use only copper wires to wire the connection terminals.

10.5.3 Connecting 24 V DC

External power supply unit
A 24 V voltage supply supplies the CDI+ splitter.
Use the Bosch Rexroth power supply unit VAP01.1H-W23-024-010-NN (see
ter 5.1 "External 24 V power supply unit" on page
the external power supply unit and on the creation of overvoltage categories, re-
fer to the documentation of the power supply unit.
All lines of the 24 V voltage supply have to be routed separately from lines carry-
ing higher voltages.
NOTICE
Ensure that the PC and the CDI+ splitter are disconnected from voltage before
wiring.

10.5.4 Connecting the digital 24 V inputs SEL and MOD

Digital input SEL
A PLC usually controls this input. Wire the respective PLC output with the input
"SEL" on the CDI+ splitter.
Bosch Rexroth AG R911400465_Edition 01
Cable length
30 m max.
100 m max.
1 m max.
Destruction of terminals, insufficient contact
and loss of UL certification if no copper wires
are used.
Destruction of the CDI+ splitter due to connec-
tion under voltage.
IndraControl VAC 08.1 CDI+ Splitter
Conductor cross-sections
1.5 mm
2
(AWG 16)
0.2 mm
2
to 1.5 mm
6.0 mm
2
(AWG 9)
6). For further information on
2
(AWG 24-16)
chap-

Advertisement

Table of Contents
loading

Table of Contents