[3] Monitor output signal cable

No.
1
Is the signal cable wired by multicore cable?
2
Are the signal cables and transmission cables
wired in the same piping duct?
3
Is the power supply cable wired at least 2 inch
(5 cm) away from signal cables?
4
Is the signal cable connected to the designated
terminal block? (See Table 3-1.)
5
Is the signal cable incorrectly wired, is there a faulty
connection or are screws loose?
6
Is the output capacity of the signal cable within
rating? (See Table 3-1.)
7
Is the function selection for the external output
signal set correctly?
Table 3-1 Monitor Output Specifications
Terminal block
Function Name
Signal specifications
Output rating
Min. applicable load
[4] Function setting (See the Lossnay technical manual for details.)
No.
1
Is the main Lossnay set correctly?
2
Are the function selection switches on the circuit
board set correctly to suit the required application?
3
Is the applicable model used as the Lossnay re-
mote controller?
4
When PZ-61DR-E is used, are the function selec-
tions set correctly to suit the required application?
5
Was a function set with the function selection
switches on the circuit board after the function is
set with PZ-61DR-E?
6
Is the Lossnay address set correctly?
Check Item
TM3 [9] [10]
Operation monitor
Malfunction monitor
208 V AC, 100 mA
Check Item
Wire the cable using a 2-core cable.
Wire the signal cables away from the transmission
cables.
Wire the power supply cable at least 2 inch (5 cm)
away from the signal cables.
Connect the signal cable to the designated terminal
block.
Connect the cable securely and correctly, and tight-
en the screws firmly.
Use the signal cable within rating.
Set the function selection switches (SW2-8, 5-2,
and 5-6) on the circuit board correctly.
Set the function settings (No. 57 and 58) of PZ-
61DR-E correctly.
(See the Lossnay technical manual.)
TM3 [8] [10]
Bypass monitor or
Volt-free contact
240 V AC, 1 A
24 V DC, 1 A
5 V DC, 100 mA
Check the function selection switch (SW5-10) on
the circuit board.
When an external signal is input to multiple
Lossnay units, set one of the units in the group as
the main Lossnay (SW5-10 ON).
Set the function selection switches (SW2, SW5,
and SW7) on the circuit board correctly.
Use PZ-61DR-E or PZ-43SMF-E.
(The air conditioner remote controller including MA
controller cannot be used.)
Set the function selections correctly.
Set the function again with PZ-61DR-E.
For the function that can be set with both PZ-
61DR-E and the function selection switches, if the
function is set to other than "DIP-SW priority" with
PZ-61DR-E, setting with the function selection
switches is disabled.
Set the address setting switches (SA1 and SA2)
correctly.