Mitsubishi Electric LGH-200RVXT-E Manual

Mitsubishi Electric LGH-200RVXT-E Manual

Hide thumbs Also See for LGH-200RVXT-E:

Advertisement

Quick Links

MODEL
Heat exchange system
Heat exchanger material
Cladding
Heat insulation material
Motor
Blower
Filter
Surrounding air condition
Suction air condition
Supply fan operation under
low outdoor temperature
Function
Weight
Electrical power supply
Ventilation mode
Fan speed
Running current
[A]
Input power
[W]
SFP
[W/(L/s)]
3
Air volume
[m
/h]
[L/s]
External static Supply
[Pa]
pressure
Return
[Pa]
Exchange
Temperature
efficiency
Enthalpy Heating
[%]
Cooling
Noise
[dB]
Insulation resistance
Direct strength
■Characteristic curve
450
400
350
300
250
200
150
100
50
0
0
0
■Attention
1. The running current, the input power, the efficiency and the noise are based on the rating air volume, and 230V/50Hz.
2. Temperature exchange efficiency (%) is based on winter condition.
3. Heat recovery ventilation mode starts automatically while detecting OA temperature lower than 8℃, even Bypass mode is
selected. Remote controller continues to display "Bypass ventilation" in this case.
4. Mitsubishi Electric measures figures in the chart according to Japan Industrial Standard (JIS B 8628), therefore the
characteristic curves are measured by chamber method.
5. The noise level at 1.5m away from outlets in the 45°direction is about 13dB greater than the indicated value at fan speed
4.
6. On-site measurements by pitot tube method could be as much 20% difference from JIS test room conditions. If the
measuring point is close to sources of turbulence like bends, contractions and dampers etc., it is difficult to measure air
volume correctly. A straight duct length more than 10D (D=duct diameter or equivalent) from the source of turbulence is
recommended for correct measurement. On-site measurement should therefore be measured in accordance with BSRIA
guideline (Commissioning Air Systems. Application procedures for buildings AG3/89.3(2001)).
SPECIFICATIONS
LGH-200RVXT-E
Heat recovery ventilating system
Special treated paper plate heat exchanger
Galvanized steel sheet
Self-extinguishing urethane foam
EC motor
245mm diameter centrifugal fan
Non-woven fabrics filter (Gravitational method 82% EU-G3)
Shall be between -10℃ and 40℃, 80%RH or less
Shall be lower than 40℃, 80%RH
-10℃ to -15℃ : Intermittent operation 60 min ON, 10 min OFF.
-15℃ or less : Intermittent operation 55 min OFF, 5 min ON.
Heat recovery ventilation/ Bypass ventilation, Fan speed 1,2,3,4
159kg
220-240V/50Hz, 220V/60Hz
Heat recovery mode
SP4
SP3
5.40
2.70
1,000
494
1.8
1.2
2,000
1,500
556
417
175
98
100
56
80.0
81.0
72.5
73.5
70.0
71.0
39.5
35.5
10MΩ or more
AC 1500V 1 minute
SP3
SP2
SP1
500
1000
200
DATE
15-Oct-2015
SP2
SP1
SP4
1.10
0.39
5.00
197
56
916
0.7
0.4
1.6
1,000
500
2,000
278
139
556
44
11
175
25
6
100
82.5
84.0
77.0
83.0
74.5
80.5
28.0
22.0
40.5
Temperature
Enthalpy heating
Enthalpy cooling
SP4
1500
2000
2500
400
600
Air volume
※Specification may be subject to change without notice.
TYPE
CEILING RECESSED LOSSNAY
MODEL
LGH-200RVXT-E
N15HHGU0029B
NUMBER
SIGN
Bypass mode
SP3
SP2
2.20
0.85
407
150
1.0
0.5
1,500
1,000
417
278
98
44
56
25
-
-
-
-
-
-
-
-
-
34.5
27.0
90
80
70
60
50
40
Supply
30
Return
20
10
0
3000
3
(m
/h)
(L/s)
800
SP1
0.34
45
0.3
500
139
11
6
-
-
-
20.5
1/5

Advertisement

loading

Summary of Contents for Mitsubishi Electric LGH-200RVXT-E

  • Page 1 3. Heat recovery ventilation mode starts automatically while detecting OA temperature lower than 8℃, even Bypass mode is selected. Remote controller continues to display "Bypass ventilation" in this case. 4. Mitsubishi Electric measures figures in the chart according to Japan Industrial Standard (JIS B 8628), therefore the characteristic curves are measured by chamber method.
  • Page 2: Outline Drawings

    7. Inspection opening (600×600mm or more) must be installed on the filter and Lossnay core removal side and under the fan motor maintenance cover. ※Specification may be subject to change without notice. DATE TYPE CEILING RECESSED LOSSNAY OUTLINE DRAWINGS 15-Oct-2015 MODEL LGH-200RVXT-E N15HHGU0029B NUMBER...
  • Page 3: Wiring Diagrams

    6. Select proper circuit breaker according to the electrical current information in the chart below. Maximum current w hen operating [A] Inrush current after 10ms 12.1 pow er supply ON [A] 100ms ※Specification may be subject to change without notice. DATE TYPE CEILING RECESSED LOSSNAY WIRING DIAGRAMS 15-Oct-2015 MODEL LGH-200RVXT-E N15HHGU0029B NUMBER...
  • Page 4: Safty Notes

    Lossnay unit, make sure to install safety equipment for the external devices. (It could cause fire, damage, etc. without safety equipment) ※Specification may be subject to change without notice. DATE TYPE CEILING RECESSED LOSSNAY SAFTY NOTES 15-Oct-2015 MODEL LGH-200RVXT-E N15HHGU0029B NUMBER...
  • Page 5 - Lossnay core (Around 10 years with maintenance at stated periods.) - Air filter (Around 5 years with maintenance at stated periods) ※Specification may be subject to change without notice. DATE TYPE CEILING RECESSED LOSSNAY SAFTY NOTES 15-Oct-2015 MODEL LGH-200RVXT-E N15HHGU0029B NUMBER...
  • Page 6 Related Links Model Number: LGH-200RVXT-E LGH-150-250RVXT-E Declaration Of Conformity LGH-150-250RVXT-E Installation Manual (1509876HC8401) LGH-150-250RVXT-E Instruction Book (1509876HC8301) LGH-150-250RVXT-E Service Manual (U213) LGH-150-250RVXT-E Technical Manual (N15HHGT0033) LGH-200RVXT-E Specification (N15HHGU0029B) Lossnay RVX(T) Quick Reference Guide...