Mitsubishi Electric LGH-250RVXT-E Handbook

Mitsubishi Electric LGH-250RVXT-E Handbook

Lossnay energy recovery ventilator

Advertisement

LOSSNAY
HANDBOOK
MODELS
LGH-150RVXT-E
LGH-200RVXT-E
LGH-250RVXT-E
Remote controller
PZ-61DR-E
Filter
(Optional)
PZ-150RTF-E
PZ-250RTF-E
Warning:
Repair work must be performed by the manufacturer, its service
agent or a similarly qualified person in order to avoid hazards.
(Optional)
March 2016
Nameplate
No. U213

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Electric LGH-250RVXT-E

  • Page 1 March 2016 No. U213 LOSSNAY HANDBOOK MODELS Nameplate LGH-150RVXT-E LGH-200RVXT-E LGH-250RVXT-E Remote controller (Optional) PZ-61DR-E Filter (Optional) PZ-150RTF-E PZ-250RTF-E Warning: Repair work must be performed by the manufacturer, its service agent or a similarly qualified person in order to avoid hazards.
  • Page 2: Table Of Contents

    3. Outside dimensions ..............5 4. Electrical wiring diagrams ............6-7 5. Circuit board diagrams ............. 8-9 6. Troubleshooting ..............10-34 7. Overhauling procedures ............35-51 8. Parts catalog ................ 52-82 LGH-150RVXT-E ............53-62 LGH-200RVXT-E ............63-72 LGH-250RVXT-E ............73-82...
  • Page 3: Safety Precautions

    1. Safety precautions Read the following precautions thoroughly before the maintenance, and then inspect and repair the product in a safe manner. The types and levels of danger that may arise if the product is handled incorrectly are described with the warning symbols shown below.
  • Page 4: Specifications

    *Temperature exchange efficiency (%) are based on winter condition. * Mitsubishi Electric measures products according to Japan Industrial Standard (JIS B 8628), therefore Q-H curves are meas- ured by chamber method. * On-site commissioning measurements by pitot tube method could be as much 20% different from JIS test room conditions. If the measuring point is close to sources of turbulence like bends, contractions and dampers etc, it is difficult to measure air vol- ume correctly.
  • Page 5: Outside Dimensions

    3. Outside dimensions LGH-150RVXT-E, LGH-200RVXT-E, LGH-250RVXT-E Air exhaust fan (Outside) Air exhaust fan (Inside) By-pass damper plate Ceiling suspension fixture (6-15 X 30 oval) Flange 1500 Flange Exhaust (outside air (exhaust air intake) outlet) Pipe guide Supply (return air) (supply air)
  • Page 6: Electrical Wiring Diagrams

    4. Electrical wiring diagrams LGH-150RVXT-E, LGH-200RVXT-E * TM1, TM2, TM3, TM4, TB5 shown in dotted lines are fi eld work. * Be sure to connect the earth wire. Model LGH-150RVXT-E LGH-200RVXT-E * A power supply isolator must be installed. Maximum current when operating 5.6 A 6.4 A * Always use an isolator for the main switch power connection.
  • Page 7 LGH-250RVXT-E * TM1, TM2, TM3, TM4, TB5 shown in dotted lines are field work. * Be sure to connect the earth wire. Model LGH-250RVXT-E * A power supply isolator must be installed. Maximum current when operating 10.8 A * Always use an isolator for the main switch power connection.
  • Page 8: Circuit Board Diagrams

    5. Circuit board diagrams Circuit board diagram and check points ( 1 ) Control circuit board Malfunction monitor output Bypass monitor output Remote controller (Between 8 and 0) Pre-heater output power supply indicator (Between 7 and 0) (LED3 Green) Error: 0 Normal: During bypass mode or Fed with power: lit...
  • Page 9 ( 2 ) Power circuit board Caution: The power circuit board is not insulated from the power line (high voltage part), except for the connection part (CN118,CN119, and CN121) with the control circuit board. Also, even when the power supply is cut off, the capacitor is charged.
  • Page 10: Troubleshooting

    The part names in the texts are standardized with the part names in the parts catalog. (There are some exceptions.) 6-1 Service flowchart After checking the check items below, follow the troubleshooting for servicing. Applicable Device Applicable Model Lossnay Energy Recovery Ventilator LGH-150RVXT-E, LGH-200RVXT-E, LGH-250RVXT-E Lossnay Remote Controller PZ-61DR-E, PZ-43SMF-E Preliminary check item Details 1 Product information •...
  • Page 11 Lossnay does not work after installation is (1) Failure mode 1: Lossnay does not work. completed. Lossnay does not work in trial operation after installation is completed, or Lossnay stops working during use. The remote controller does not work after (2) Failure mode 2: The remote controller does not installation is completed.
  • Page 12 2 Transmission cables (remote controller transmission cable, M-NET transmission cable, and external input/ output signal cable) Check Item Corrective action 1 Are the designated cables used for the remote control- Use the designated transmission cables. ler transmission cable and M-NET transmission cable? (See Table 2-1 and Table 2-2.) 2 Are the designated cables used for the external input/ Use the designated cables.
  • Page 13 Table 2-3 External input/output specifications Terminal or Signal Total Function Name connector on Materials Used specifications extension the circuit board External control input Level/pulse Single-lead 0.8 to 1.2 mm dia. or 500 m TM2 1 3 (volt-free contact) (Note 1) twisted lead 0.5 to 1.5 mm External control input Level/pulse...
  • Page 14 3 Monitor output signal cable Check Item Corrective action 1 Is the signal cable wired by multicore cable? Wire the cable using a 2-core cable. 2 Are the signal cables and transmission cables wired Wire the signal cables away from the transmission in the same piping duct? cables.
  • Page 15 5 LED Indications on the circuit board Contents Check Item Corrective action LED1 Lossnay main unit Blinking: Starting up, or error oc- See Failure Mode 5. (green) error indicator curred Lit: During delay operation Lossnay operates after the delay time has passed.
  • Page 16 Individual function check items If Lossnay does not work in the trial operation after installation is completed, or if Lossnay stops working dur- ing use, check the following items. Problem Factor Corrective action 1 The fan does not The connector between the fan Check the connector (CN9) for the exhaust fan operate even motor and circuit board is discon-...
  • Page 17 Problem Factor Corrective action 3 The fan does not The pre-heater or operation moni- If the pre-heater or operation monitor with delay stop even though tor with delay operation is set to operation is set to be used, the fan continues op- the remote control- be used.
  • Page 18 Problem Factor Corrective action 8 Even though the The outdoor temperature is 8°C When the outdoor temperature is 8°C or lower, remote controller is or lower. the ventilation mode is fixed to the Energy re- operated to change covery mode. the ventilation mode, The signal is input to the Bypass Check the Bypass mode switching input (CN26...
  • Page 19 (2) Failure mode 2: The remote controller does not work. If the remote controller does not work after installation is completed, check the following items. 1 PZ-61DR-E Problem Factor Corrective action 1 Nothing is displayed The power of the Lossnay unit is Check the items described in (1) 1.
  • Page 20 Problem Factor Corrective action 3 It takes time for the The Lossnay unit is starting up. The remote controller is not fed with power dur- remote controller to ing start-up of the Lossnay unit for a maximum be fed with power of one minute.
  • Page 21 Individual check items If the system cannot be started/stopped using the remote controller after installation is completed, check the following items. 1 PZ-61DR-E Problem Factor Corrective action 1 Some Lossnay units The power of the Lossnay unit is Check the items described in (1) 1. in the group do not not ON.
  • Page 22 2 Interlocking with air conditioners (Mr. Slim indoor unit or City Multi indoor unit) or external devices Problem Factor Corrective action 1 Lossnay interlock The power of the Lossnay unit is Check the items described in (1) 1. settings cannot be not ON.
  • Page 23 3 System controller Problem Factor Corrective action 1 The group of The power of the Lossnay unit is Check the items described in (1) 1. Lossnay cannot be not ON. set with the system M-NET transmission cable is con- Connect the M-NET transmission cable to the controller.
  • Page 24 (4) Failure mode 4: Lossnay does not work properly. Initial Check Items If Lossnay does not work properly after installation is completed, check the following items. Check item Notes 1 Are the function selection switches Depending on the settings of the function selection switches, (SW2 and SW5) on the Lossnay Lossnay may automatically operate or stop, or specific operation circuit board set correctly to suit the...
  • Page 25 Problem Factor Corrective action 2 Even though the The outdoor temperature is 8°C When the outdoor temperature is 8°C or lower, remote controller is or lower. the ventilation mode is fixed to the Energy re- operated to change covery mode. the ventilation The signal is input to the Bypass Check the Bypass mode switching input (CN26...
  • Page 26 (5) Failure mode 5: Error code and LED display An error code displayed on the remote controller (PZ-61DR-E, PZ-43SMF-E) or the M-NET controller, and blinking or illumination of LED1 (green) or LED2 (red) on the circuit board show the type of an error. The LED blink interval is 0.25 seconds for both on and off.
  • Page 27 (inside) connector (CN10) on tor (inside) the Power circuit board 1 (Centrifugal fan <For LGH-250RVXT-E> Check the connector (CN10) con- does not work, Faulty connection of the supply fan nection. insufficient motor (inside) connector (CN10) on...
  • Page 28 (inside) connector (CN9) on motor (inside) the Power circuit board 1 (Centrifugal fan <For LGH-250RVXT-E> Check the connector (CN9) con- does not work, Faulty connection of the exhaust fan nection. insufficient motor (inside) connector (CN9) on...
  • Page 29 (outside) connector (CN9) on motor (out- the Power circuit board 2 side) <For LGH-250RVXT-E> Check the connector (CN9) con- (Centrifugal fan Faulty connection of the exhaust fan nection. does not work, motor (outside) connector (CN9) on...
  • Page 30 Error LED1 LED2 Symptom Cause Corrective action Code (green) (red) 5101 Outdoor air Faulty connection of the thermis- Check the connector (CN22) con- blinks (OA) thermis- tor connector (CN22) on the control nection. tor related circuit board error Thermistor failure Disconnect the connector (CN22), and check the resistance of the thermistor.
  • Page 31 Error LED1 LED2 Symptom Cause Corrective action Code (green) (red) 6603 Transmission Faulty connection of the M-NET Check the items described in (1) blinks error transmission cable (transmission Wiring was performed with power Restart the system after complet- • bus busy) still supplied to the M-NET transmis- ing wiring.
  • Page 32 Error LED1 LED2 Symptom Cause Corrective action Code (green) (red) 6801 PZ-43SMF-E Multiple PZ-43SMF-E transmission Using the applicable cable, wire blinks communica- cables are wired using multicore the transmission cable away from tion error cables. one another. The power supply cable is too close Wire the power supply cable at to the PZ-43SMF-E transmission least 5 cm away from the trans-...
  • Page 33 Error LED1 LED2 Symptom Cause Corrective action Code (green) (red) 6833 PZ-61DR-E Faulty connection of the PZ-61DR-E Check the items described in (1) blinks communica- transmission cable tion error If the error re-occurs, check for (hardware noise on the transmission cable. error) If the above does not correct the problem, replace the Lossnay...
  • Page 34 LGH-150RVXT-E, LGH-200RVXT-E Lead color Black-Red Black-White Black-Yellow Black-Blue Normal resistance ∞ Ω About 50 kΩ About 150 kΩ ∞ Ω LGH-250RVXT-E Lead color Black-Red Black-White Black-Yellow Black-Blue Normal resistance About 1 MΩ About 48 kΩ About 155 kΩ ∞ Ω...
  • Page 35: Overhauling Procedures

    7. Overhauling procedures Work precautions • When touching the electric components such as circuit boards and fan motors, do not touch the components for more than 5 minutes after power-off, and then start working. If LED4 on the circuit board is lit, do not touch the electric components.
  • Page 36 2 Check that LED4 on the control circuit board is OFF. LED 4 Control circuit board 3 Unscrew the screws (eight PTT screws 4×8, indicated by ) for the maintenance cover (for the motors) on the bot- tom side of the main unit. Maintenance cover (for the motors) 4 Open the maintenance cover (for the motors).
  • Page 37 Even when the fan motor is stopped, disconnecting the live-line connectors will cause a motor malfunction. For LGH-250RVXT-E 7 Unscrew the screws (four PTT screws 5×10, indicated by ) for the fan base of the air supply fan (outside unit).
  • Page 38 Note: Remove the other motors in the same way. For LGH-150RVXT-E and LGH-200RVXT-E (Six PTT screws 5×10, indicated by ) Motor Motor fix plate For LGH-250RVXT-E (Six PTT screws 5×10, indicated by ) Motor Motor fix plate ( 3 ) Terminal block parts 1 Unscrew the screws (four PTT screws 4×8, indi-...
  • Page 39 2 Check that LED4 on the control circuit board is OFF. 3 Disconnect the connectors (indicated by ) from the power circuit boards and reactors. For LGH-150RVXT-E and LGH-200RVXT-E For LGH-250RVXT-E Reactor Control circuit board Reactor Control circuit board LED 4...
  • Page 40 (5) Power circuit boards For LGH-150RVXT-E and LGH-200RVXT-E 1 Remove the control cover. → See (3) 1. Power circuit board 1 Control circuit board (LG-X05DC-E . P) (LG-X05DC-E . C) 2 Check that LED4 on the control circuit board is OFF, and then disconnect the connectors (indicated by ) from the power circuit boards.
  • Page 41 For LGH-250RVXT-E 1 Remove the control cover. → See (3) 1. 2 Check that LED4 on the control circuit board is OFF, and then disconnect the connectors (indicated by ) from the power circuit boards. Precaution Top right power circuit board is different from the other power circuit boards.
  • Page 42 (6) Reactors For LGH-150RVXT-E and LGH-200RVXT-E 1 Remove the control cover. → See (3) 1. 2 Check that LED4 on the control circuit board is OFF. → See (2) 2. 3 Unscrew the screws (six PTT screws 4×8, indicated by ), and remove the control base from the main unit.
  • Page 43 5 Unscrew the screws (two PT screws 4×8 for each, indi- Reactor (Yellow) cated by ) to remove the reactors. Note: LGH-250RVXT-E Lossnay has ten reactors. Assembly precaution Number indications are attached on the lead wires. When replacing the reactors, install them to the correct position, and reconnect the lead wires according to the numbers shown in the picture.
  • Page 44 ( 7 ) Lossnay cores and GM assemblies 1 Unscrew the black screw (one special screws 4×8, indi- cated by ) for the fix piece. Fix piece Maintenance cover 2 Slide the fix piece toward the left side. Fix piece 3 Disengage the hinges, and open the maintenance cover.
  • Page 45 For LGH-250RVXT-E 8 Unscrew the screws (two PTT screws 4×8, indicated by ) to remove the GM assembly from the main unit. Note: LGH-250RVXT-E Lossnay has two GM assem- blies. See 9 and 0 for removing the other GM assembly.
  • Page 46 For LGH-250RVXT-E 9 Unscrew the screws (two PTT screws 4×8, indicated by ) to remove the GM assembly from the main unit. GM assembly GM assembly For LGH-250RVXT-E 0 Unscrew the screws (two PTT screws 4×8, indicated by ) to remove the GM plate from the GM assembly.
  • Page 47 ( 8 ) Thermistors 1 Remove the cover. → See (7) 1 to 6. 2 Disconnect the thermistor connectors. Connector for Connector for the thermistor (RA) the thermistor (OA) 3 Unfasten the clampers, and remove the thermistors. Clamper Thermistor (OA) Thermistor (RA) Clamper When reassembling...
  • Page 48 (9) Procedures for replacing the circuit boards Notes • Before removing the circuit boards for replacement, check the following Steps 1 and 2. • When the Lossnay remote controller PZ-61DR-E is connected, make sure to replace the circuit boards as described in the Steps.
  • Page 49 Step Details Check item Removing the circuit boards • For the working precautions, see page 35. • For removing the circuit boards, see (4) Control circuit board (page 39) or (5) Power circuit boards (page 40 and 41). Attaching the circuit boards Address set- 1 According to the function status record data prepared in Step 3, set the address ting...
  • Page 50 Step Details Check item Function setting with PZ-61DR-E When PZ-61DR-E is connected, according to the function status record data pre- Address set- pared in Step 2, set the function settings with PZ-61DR-E. ting If PZ-61DR-E is not connected, skip this step and proceed to Step 7. Function set- To perform function settings with PZ-61DR-E, see the Lossnay technical manual or ting...
  • Page 51 □ □ □ □ □ □ LGH-150RVXT-E □ □ □ □ □ □ LGH-200RVXT-E □ □ □ □ □ □ LGH-250RVXT-E □ □ □ □ □ □ □ □ □ □ □ □ □ □ □ □ □ □ □...
  • Page 52: Parts Catalog

    8. Parts catalog Please note the following when using the parts catalog. 1. When ordering parts, always indicate the part number, part name, and the number of parts required. 2. It may take time for you to receive the parts. Make an inquiry about a rush order. 3.
  • Page 53: Lgh-150Rvxt-E

    LGH-150RVXT-E 4 pcs. 4 pcs. 4 pcs. 4 pcs. <When using the duct flange 250x750> 2 pcs. 2 pcs. 2 pcs. 2 pcs. 6 pcs. 2 pcs. 6 pcs. 2 pcs. 6 pcs. 6 pcs. 2 pcs. 2 pcs. 2 pcs. 2 pcs.
  • Page 54 LGH-150RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety Maintenance cover Y50 174 708 Air filter (RA) Y50 174 718  Lossnay core Y50 174 710  Air filter (OA) Y50 174 717  Fix piece Y50 123 722 Hinge R50 466 344 Special screw 4×8...
  • Page 55 2 pcs. 2 pcs. Air supply fan assembly (SA) 4 pcs. Outside unit 4 pcs. Inside unit 4 pcs. 4 pcs. Note: Air exhaust fan assembly (EA) consists of the same components. <Standard screws> Symbol Screw name PTT screw 4x8 PTT screw 5x10 PTT screw 4x25 ─...
  • Page 56 LGH-150RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 21 Cord bush M45 649 226 22 Connector plate Y50 115 710 23 Connector cover Y50 115 709 24 Special nut (M12) R50 218 067 Left-handed 25 Tab washer Y50 171 707 26 Centrifugal fan Y50 171 480...
  • Page 57 2 pcs. <Standard screws> Symbol Screw name PTT screw 4x8 ─ 57 ─ LGH-150RVXT-E...
  • Page 58 LGH-150RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 41 Cover K81 636 390 With a Cord bush 42 Cord bush K81 636 225 43 Gm assembly Y50 174 260  AC220・240V ─58─...
  • Page 59 2 pcs. 2 pcs. 2 pcs. 2 pcs. 2 pcs. <Standard screws> Symbol Screw name PTT screw 4x8 PT screw 6x12 PT screw 4x8 PTT screw 4x20 PTT screw 3x8 ─ 59 ─ LGH-150RVXT-E...
  • Page 60 LGH-150RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 61 Circuit board Y50 169 173 LG-X05DC-E・C  62 PCB fix plate Y50 169 380 63 Terminal block Y50 174 216  With the lead wires 64 Reactor Y50 172 179 ...
  • Page 61 (*1) MAX 240 V AC 1 A MIN 220 V AC 100 mA Bypass monitor or Pre- 24 V DC 1 A 5 V DC 100 mA heater signal output (*1) Malfunction monitor CN20(GR) output (*1) Printed Circuit Board 1 Operation monitor (Power circuit board 1) output (*1)
  • Page 62 LGH-150RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 81 Lead wire Y50 174 215 CN21  82 Lead wire Y50 174 214 CN19  83 Lead wire Y50 174 213  CN18 84 Thermistor (OA) Y50 174 217 -30℃...
  • Page 63: Lgh-200Rvxt-E

    LGH-200RVXT-E 4 pcs. 4 pcs. 4 pcs. 4 pcs. <When using the duct flange 250x750> 2 pcs. 2 pcs. 2 pcs. 2 pcs. 6 pcs. 2 pcs. 6 pcs. 2 pcs. 6 pcs. 6 pcs. 2 pcs. 2 pcs. 2 pcs. 2 pcs.
  • Page 64 LGH-200RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety Maintenance cover Y50 174 708 Air filter (RA) Y50 174 720  Lossnay core Y50 174 710  Air filter (OA) Y50 174 719  Fix piece Y50 123 722 Hinge R50 466 344 Special screw 4×8...
  • Page 65 2 pcs. 2 pcs. Air supply fan assembly (SA) 4 pcs. Outside unit 4 pcs. Inside unit 4 pcs. 4 pcs. Note: Air exhaust fan assembly (EA) consists of the same components. <Standard screws> Symbol Screw name PTT screw 4x8 PTT screw 5x10 PTT screw 4x25 ─...
  • Page 66 LGH-200RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 21 Cord bush M45 649 226 22 Connector plate Y50 115 710 23 Connector cover Y50 115 709 24 Special nut (M12) R50 218 067 Left-handed 25 Tab washer Y50 171 707 26 Centrifugal fan Y50 171 480...
  • Page 67 2 pcs. <Standard screws> Symbol Screw name PTT screw 4x8 ─ 67 ─ LGH-200RVXT-E...
  • Page 68 LGH-200RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 41 Cover K81 636 390 With a Cord bush 42 Cord bush K81 636 225 43 Gm assembly Y50 174 260  AC220・240V ─68─...
  • Page 69 2 pcs. 2 pcs. 2 pcs. 2 pcs. 2 pcs. <Standard screws> Symbol Screw name PTT screw 4x8 PT screw 6x12 PT screw 4x8 PTT screw 4x20 PTT screw 3x8 ─ 69 ─ LGH-200RVXT-E...
  • Page 70 LGH-200RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 61 Circuit board Y50 169 173 LG-X05DC-E・C  62 PCB fix plate Y50 169 380 63 Terminal block Y50 174 216  With the lead wires 64 Reactor Y50 172 179 ...
  • Page 71 (*1) MAX 240 V AC 1 A MIN 220 V AC 100 mA Bypass monitor or Pre- 24 V DC 1 A 5 V DC 100 mA heater signal output (*1) Malfunction monitor CN20(GR) output (*1) Printed Circuit Board 1 Operation monitor (Power circuit board 1) output (*1)
  • Page 72 LGH-200RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 81 Lead wire Y50 174 215 CN21  82 Lead wire Y50 174 214 CN19  83 Lead wire Y50 174 213  CN18 84 Thermistor (OA) Y50 174 217 -30℃...
  • Page 73: Lgh-250Rvxt-E

    LGH-250RVXT-E 4 pcs. 4 pcs. 4 pcs. 4 pcs. <When using the duct flange 250x750> 2 pcs. 2 pcs. 2 pcs. 2 pcs. 6 pcs. 2 pcs. 6 pcs. 2 pcs. 6 pcs. 6 pcs. 2 pcs. 2 pcs. 2 pcs.
  • Page 74 LGH-250RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety Maintenance cover Y50 174 708 Air filter (RA) Y50 174 720  Lossnay core Y50 174 710  Air filter (OA) Y50 174 719  Fix piece Y50 123 722...
  • Page 75 Outside unit 4 pcs. Inside unit 4 pcs. 4 pcs. 4 pcs. Note: Air exhaust fan assembly (EA) consists of the same components. <Standard screws> Symbol Screw name PTT screw 4x8 PTT screw 5x10 PT screw 6x20 ─ 75 ─ LGH-250RVXT-E...
  • Page 76 LGH-250RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 21 Cord bush M45 649 226 22 Connector plate Y50 115 710 23 Connector cover Y50 115 709 24 Special nut (M12) R50 218 067 Left-handed 25 Washer (12)
  • Page 77 2 pcs. 2 pcs. 2 pcs. <Standard screws> Symbol Screw name PTT screw 4x8 ─ 77 ─ LGH-250RVXT-E...
  • Page 78 LGH-250RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 41 Cover K81 636 390 With a Cord bush 42 Cord bush K81 636 225 43 Gm assembly Y50 174 260  AC220・240V ─78─...
  • Page 79 2 pcs. 2 pcs. 2 pcs. 2 pcs. 2 pcs. 2 pcs. 2 pcs. <Standard screws> 2 pcs. Symbol Screw name PTT screw 4x8 PT screw 6x12 PT screw 4x8 PTT screw 4x20 PTT screw 3x8 ─ 79 ─ LGH-250RVXT-E...
  • Page 80 LGH-250RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 61 Circuit board Y50 169 173 LG-X05DC-E・C  62 PCB fix plate Y50 169 380 63 Terminal block Y50 175 215  With the lead wires 64 Reactor Y50 172 179 ...
  • Page 81 TAB2 TH2(RA) REACTOR LED6 Isolator LINE (Field supply) CN10 CN121 FILTER Bottom left Printed SUPPLY Circuit Board (SA Outside) FAN MOTOR (Bottom left (Outside) power circuit board) POWER SUPPLY 220-240V/ 50Hz 220V/ 60Hz TAB1 TAB2 REACTOR ─ 81 ─ LGH-250RVXT-E...
  • Page 82 LGH-250RVXT-E Critical Q'ty Name of part Parts No. Remarks pcs/unit safety 81 Lead wire Y50 175 213 CN21・CN18・CN19  82 Thermistor (OA) Y50 174 217 -30℃ to 100℃  83 Thermistor (RA) Y50 174 223  -30℃ to 100℃ ─82─...
  • Page 83 Related Links Model Number: LGH-250RVXT-E Acticare, R32 Hybrid VRF, Hereford LGH-150-250RVXT-E Declaration Of Conformity LGH-150-250RVXT-E Installation Manual (1509876HC8401) LGH-150-250RVXT-E Instruction Book (1509876HC8301) LGH-150-250RVXT-E Service Manual (U213) LGH-150-250RVXT-E Technical Manual (N15HHGT0033) LGH-250RVXT-E Specification (N15HHGU0030B) Lossnay RVX(T) Quick Reference Guide...