3. Distributor type MULTI F DX (3 phase)
3.11 Electrical characteristics
Model
Type
A7UW42LFA0
[FM41AH U32]
A8UW48LFA0
Inverter
[FM49AH U32]
A9UW56LFA0
[FM57AH U32]
Notes :
1. Voltage range
Voltage supplied to the unit terminals should be within the mini-
mum and maximum range
2. Maximum allowable voltage unbalance between phase is 2 %
3. MCA / MOP
MCA = (1.25 x RLA) + Load1 + Load2
MOP = (2.25 x RLA) + Load1 + Load2
- Load1 : sum of current for all other motors
- Load2 : any other load rated 1.0A or more
4. Select wire spec. based on the MCA
5. Select proper circuit breaker as given below
MCA < Circuit breaker ≤ MOP
6. Recommended circuit breaker is ELCB (Earth Leakage circuit
breaker)
7. MSC & RLA are measured as the compressor only test condi-
tion.
8. MSC values
Unit
Hz
Voltage
Voltage range
MIN.:342
50
380-415
MAX.:456
Power
Compressor
MCA
MOP
12.2
20.8
12.3
21.0
12.5
21.3
9. RLA is measured during each individual compressor test condi-
tion.
Ex) 5.0 : RLA of (inv. comp.)
10. OFM is measured as the outdoor unit test condition
MCA : Minimum Circuit Amperes (A)
MOP : Maximum rating over current protective device
MSC : Maximum Starting Current
RLA : Rated Load Amperes (A)
OFM : Outdoor Fan Motor
kW : Fan Motor rated output (kW)
FLA : Full Load Amperes (A)
Heat pump 50Hz/R410A
OFM
RLA
KW
FLA
8.6
0.12 x 2
0.73 x 2
8.7
0.12 x 2
0.73 x 2
8.8
0.12 x 2
0.73 x 2
_ 36