Mounting The Device - Siemens SIMATIC NET Installation Manual

Hide thumbs Also See for SIMATIC NET:
Table of Contents

Advertisement

Note
For further details of the device's compliance with Class I, Division 2, Zone 2
standards, refer to
Do not disconnect or open equipment unless power has been switched off or the
area is known to be non-hazardous.
Substitution of the components may impair suitability for Class I, Division 2.
Sample Hazardous Location Label
The following is an example of the RUGGEDCOM RS900F hazardous location label:
Figure 2.1
2.4

Mounting the Device

The RUGGEDCOM RS900F is designed for maximum mounting and display flexibility.
It can be equipped with adapters that allow it to be attached to a DIN rail or panel.
RUGGEDCOM RS900F
Installation Manual, 04/2021, C79000-G8976-1350-07
The equipment shall be installed in an enclosure that is considered to be not
accessible in normal operation without the use of a tool providing a degree of
protection of not less than IP54 according to CSA/UL/IEC/EN 60079-0 and CSA/
UL/IEC/EN 60079-15. The enclosure shall have a minimum service temperature
range of -40 to 100 °C (-40 to 212 °F).
The equipment shall be used in an area of not more than pollution degree 2 as
defined in IEC/EN 60664-1.
The serial DB9 console port shall only be used in the safe area.
The equipment must be appropriately connected to safety Earth upon
installation.
"Approvals (Page
NOTICE
NOTICE
Compliance Label (Example)
33)".
Installing the Device
2.4 Mounting the Device
9