Wiegand Reader Turnstile, Single Door Contact Configuration; Wiegand Reader Turnstile, Dual Door Contact Configuration - Siemens SiPass integrated Controller And Device Installation Manual

Hide thumbs Also See for SiPass integrated:
Table of Contents

Advertisement

2.3.3.7 Wiegand Reader Turnstile,
2.3.3.8 Wiegand Reader Turnstile,
A6V11164550
Single Door Contact Configuration
Label on AP Controller
IN 1
IN 2
IN 3
IN 4
RLY 1
RLY 2
OUT 1
OUT 2
OUT 3
OUT 4
READER 1
READER 2
This configuration is not compatible with ACC-APM 12V/24V PSU Kit because IN
3 is pre-wired for power monitoring, and IN4 for cabinet tamper.
Dual Door Contact Configuration
Label on AP Controller
IN 1
IN 2
IN 3
IN 4
RLY 1
RLY 2
OUT 1
OUT 2
OUT 3
OUT 4
READER 1
READER 2
This configuration is not compatible with ACC-APM 12V/24V PSU Kit because IN
3 is pre-wired for power monitoring, and IN4 for cabinet tamper.
SiPass Point Function
Door 1 REX
Door 1 D/C
Door 2 REX
In 1
Door 1 LK
Door 2 LK
Green LED for Reader 1
Red LED for Reader 1
Green LED for Reader 2
Red LED for Reader 2
Pins A and B of READER 1 port are the data lines for
Wiegand Reader 1. D1 = A; D0 = B
Pins A and B of READER 2 port are the data lines for
Wiegand Reader 2. D1 = A; D0 = B
SiPass Point Function
Door 1 REX
Door 1 D/C
Door 2 REX
Door 2 D/C
Door 1 LK
Door 2 LK
Green LED for Reader 1
Red LED for Reader 1
Green LED for Reader 2
Red LED for Reader 2
Pins A and B of READER 1 port are the data lines for
Wiegand Reader 1. D1 = A; D0 = B
Pins A and B of READER 2 port are the data lines for
Wiegand Reader 2. D1 = A; D0 = B
Access Controllers
2
ACC-AP
23 | 38