Panasonic FP7 User Manual page 43

Analog output unit
Hide thumbs Also See for FP7:
Table of Contents

Advertisement

Unit memory
Name
address
UM00108
Analog output pro-
cessing
UM00118
UM00128
UM00138
UM00109
Range setting
UM00119
UM00129
UM00139
UM0010A
Analog output in
UM0011A
PROG mode
UM0012A
UM0013A
Offset/gain processing 16#0
Scale conversion
Upper and lower limit
clipping
UM0010B
Offset value
UM0011B
UM0012B
UM0013B
UM0010C
Gain value
UM0011C
UM0012C
UM0013C
UM0010D
Scale conversion max.
UM0011D
value
UM0012D
UM0013D
UM0010E
Scale conversion min.
UM0011E
value
UM0012E
UM0013E
UM0010F
Upper limit clipping
UM0011F
value
UM0012F
UM0013F
UM00100
Lower limit clipping
UM00120
value
UM00130
UM00140
UM 00111
Digital input value in
UM 00121
PROG mode
UM 00131
UM 00141
FP7 Analog Output Unit User's Manual
Default Setting range
16#1
16#0: Disable
16#1: Enable
16#1
16#1: Voltage output -10 to +10V
16#2: Voltage output 0 to +10V
16#4: Voltage output 0 to +5V
16#8: Voltage output +1 to + 5V
16#10: Current output 0 to +20mA
16#20: Current output +4 to +20mA
16#0
Bit 0-3
Bit 4–7
16#0
Bit 8–11
16#0
Bit 12–15
0
To apply the setting, "Offset/gain processing" must be
enabled.
Setting range: -3000 to +3000 (specified with a signed
integer)
10000
To apply the setting, "Offset/gain processing" must be
enabled.
Setting range: +9000 to +11000: 0.9x to 1.1x (speci-
fied with a signed integer)
10000
To apply the setting, "Scale conversion" must be ena-
bled.
Setting range: -30000 to +30000 (specified with a
signed integer)
0
To apply the setting, "Scale conversion" must be ena-
bled.
Setting range: -30000 to +30000 (specified with a
signed integer)
0
To apply the setting, "Limit alarm" must be enabled.
Setting range: -32500 to +32500 (specified with a
signed integer)
0
0
Setting range:
-10...+10V: -32500 to +32500
0...+10V/0...+5V/0...+20mA: 0 to +32500
+1...+5V/+4...+20mA: 0 to +25000
(specified with a signed integer)
16#0: Stop output (output FALSE)
16#1: Hold current value
16#2: Hold user-defined value
16#0: Disable
16#1: Enable
16#0: Disable
16#1: Enable
16#0: Disable
16#1: Enable