Hardware
4.1 Technical requirements
NOTICE
Component damage caused by excessively low current carrying capacity of the DC link
busbars
The DC link busbars of the individual components have different current carrying capacities.
If more current flows through a DC link busbar than is specified for it, the component will heat
up strongly and may sustain damage as a result of overheating.
● When configuring the drive lineup, carefully observe the current carrying capacities of the
● If required, replace the DC link jumper or reduce the load.
Figure 4-1
Example hardware layout for crane systems with SINAMICS S120 Motor Modules Booksize 200 A
24
individual components.
Motor Modules Booksize parallel connection
Application Manual, 01/2020, 6SL3097-5BF00-0BP0