ABB TS3 Instruction Manual page 36

Trip unit test set
Table of Contents

Advertisement

Example of test on PR232:
Current generation on phase L1
Setting on the trip unit for L, S, I protections.
Protection
L
S
I
Table 17
TS3
888.902.6111
Trip
Curve
Trip time
threshold
2
t=k/I
I1= 0.4In
3s
t=k
I2=5In
t2 = 0.25s
I3=7In
1SDH000670R0002
www.intellirentco.com
|
Expected
I test
tripping
time
2.4In
3s
6In
0,25s
 60ms
8.4In
L3852
36/44