Q U i c k s ta r t g U i D e ( i n s ta l l at i o n n ot e s )
Location
07
Install of The ArcSwitch Panel Unit ™ indoors, in a
Panel mounting
ArcSwitch Panel Unit
place protected from water splashes and sun
rays. Do not place near heat sources exceeding
08
the parameters stated in this manual. Position on
ArcSwitch Panel Unit
a stable surface, far from any possible vibrations.
rear electrical connector
Position the ArcSwitch Panel Unit™ so it can be
reached by an operator without the use of a
ladder.
Repairs
Do not open the ArcSwitch Panel Unit™ For any
fault, there is no service usable parts inside. The
opening of the ArcSwitch Panel Unit™ and or the
removal of the warranty label entails the
automatic forfeiture of the warranty. The
Warranty seal is applied to all devices.
Fitting the panel unit
The ArcSwitch Panel Unit™ must be fitted on a LV
control panel and is designed for indoor use
only and it should be fitted by a Qualified
Electrician complying with the following
instructions:
07
First cut out a 92 mm x 92 mm hole in the control
panel and be aware not to damage existing wiring
when retrofitting.
If you are cutting metal beware of metal swarf
and clean as you go.
Fit the ArcSwitch Panel Unit™ into the cutout and
secure with the blocks supplied.
You can connect ArcSwitch Panel Unit™ by
paralleled across the open and close buttons
Wire up the rear terminals as follows
• Ground, To the ground / Earth on door
• + DC feed wire to the Com terminal
• Switched wire to the Close terminal
• Switched wire to the Open terminal
When wiring up the ArcSwitch Panel Unit™ DO
NOT wire it in a fashion where electrical control
interlocks are bypassed as this could cause injury
or death.
Rear electrical connections
The Connections on the rear of the ArcSwitch
Panel Unit™
• Common terminal is connected to the DC
Positive Feed.
• Ground terminal is connected to Ground /
Earth.
• Close terminal is connected to the switched
side of the closing button.
• Open terminal is connected to the switched
side of the opening button.
Polarity needs to be observed because you are
switching the dc positive through the Portable
ArcSwitch Meter™ to the opening and closing
coils.
08
Front electrical connections
The Connections on the front of the ArcSwitch
Panel Unit™
• COM is connected to the COM on the Portable
ArcSwitch Meter™
• Ground is connected to Ground on the Portable
ArcSwitch Meter™
• Close output is connected to Close output on
the Portable ArcSwitch Meter™
• Open output is connected to the Open output
on the Portable ArcSwitch Meter™
All connections on the front of the ArcSwitch
panel Unit™ to the Portable ArcSwitch Meter™
should be made by the leads provided in the
Portable ArcSwitch Meter kit™
17