Recloser setting:
301
NUMBER OF RECLOSING ATTEMPTS:
302
RECLOSING WAIT CONDITIONS:
303
TIME DELAY FOR THE FIRST RECLOSING ATTEMPT:
304
TIME DELAY FOR
ATTEMPT:
TIME DELAY FOR THIRD RECLOSING ATTEMPT:
305
306
TIME DELAY FOR RECLOSING CONDITIONS:
307
DWELL TIME:
308
RESET TIME:
Event masks:
003
EVENT MASK:
- If the calibration deteriorates:
The protection substitutes the deteriorated calibration for the default calibration
and the DEFAULT CALIBRATION BY signal is activated.
The calibration loss implies the need to recalibrate the relay in the factory. Since it
is not always possible to immediately disconnect the relay and send it back to the factory
so that it can be recalibrated, using the default calibration settings is acceptable as long
as the default calibration setting is maintained below 5% error. However, it is not
advisable to postpone the recalibration longer than absolutely necessary.
Cold/warm boot
Any system reset causes a cold boot. During this boot the self checks are
performed. If no critical errors are detected a warm boot is performed.
During a warm boot the system variables and parameters are initiated and the
corresponding LED on the front panel of the relay is lighted.
Cold boots as well as warm boots are saved as events.

4.18 OUTPUTS

The external connections of the MLP may be seen in figures 3.1 to 3.12.
Non-seleccionable outputs:
The relay includes the following non-seleccionable output contacts:
Two trip contacts.
Two closing contacts (RCL).
Alarm equipment.
Transmission initiate (XMTR).
Seleccionable outputs:
GEK-98846A
THE
SECOND
RECLOSING
40
Disable (0)
NO
0.2 s
0.2 s
0.2 s
0.1 s
0.1 s
0.1 s
All allowed