Outputs; Communications; Environmental - GE Multilin MIGII Instruction Manual

Digital protection for electrical machines
Table of Contents

Advertisement

2 PRODUCT DESCRIPTION
2.16.5.1 OUTPUT RELAYS
Configuration:
Contact Material:
Maximum Operating Voltage:
Continuous Mode Current:
Make and Carry:
Breaking:
Max. Ratings for 100.000 operations:
VOLTAGE
DC Resistive
24 Vdc
48 Vdc
125 Vdc
250 Vdc
AC Resistive
120 Vac
250 Vac
AC Inductive
PF = 0.4
250 Vac
FRONT PORT
REAR PORT
Operating Temperatures:
Ambient Storage Temperatures:
Maximum relative humidity
Altitude
Pollution Degree
GEK-113188A
6 Electro-Mechanical Form C
Silver alloy suited for inductive loads
440 Vac
16 A at 250 Vac. general purpose
¾ HP, 124 Vac
1-1/2 HP, 250 Vac
10A, 250 Vac, 0.4 PF,
B300 pilot duty
48 A
4000 VA
MAKE&CARRY
MAKE&CARRY 0.2 SEC
CONTINUOUS
16 A
16 A
16 A
16 A
16 A
16 A
10 A
RS232
RS485
-20º C to +60º C
-40º C to +80º C
95%
2000 m. Max
2
MIGII Digital Protection for Electrical Machines
2.16 TECHNICAL SPECIFICATIONS.
BREAK
48 A
16 A
48 A
2.6 A
48 A
0.6 A
48 A
0.5 A
48 A
16 A
48 A
16 A
30 A
10 A
300, 600, 1200, 2400, 4800, 9600 or 19200 bps,
Modbus® RTU
300, 600, 1200, 2400, 4800, 9600 or 19200 bps,
Modbus® RTU

2.16.5 OUTPUTS

MAX LOAD
384W
125W
75 W
125 W
1920 VA
4000 VA
1000 VA

2.16.6 COMMUNICATIONS

2.16.7 ENVIRONMENTAL

2-25
2