Advanced Settings; Phase / Ground Toc Settings (51P / 51G) (Table 2); Phase / Ground Ioc Settings (50P / 50G) (Table 2) - GE Multilin MIGII Instruction Manual

Digital protection for electrical machines
Table of Contents

Advertisement

9.24 ADVANCED SETTINGS

9.24ADVANCED SETTINGS
GENERAL ADVANCED
SETTINGS
Identification
Active Table
Minimum tripping time
Phase TOC Function Table 2
51P Enable Table 2
51P Permission to Trip Table 2
51P Tap / Pickup Value Table 2
51P Curve Type Table 2
51P Time Dial Table 2
51P Definite Time Delay Table 2
Ground TOC Function Table 2
51G Enable Table 2
51G Permission to Trip Table 2
51G Tap / Pickup Table 2
51G Curve Type Table 2
51G Time Dial Table 2
51G Definite Time Delay Table 2
Phase IOC Setting Table 2
50P Enabling Table 2
50P Permission to Trip Table 2
50P Tap / Pickup Table 2
50P Time Delay Table 2
Ground IOC Setting Table 2
50G Enabling Table 2
50G Permission to Trip Table 2
50G Tap / PickupTable 2
50G Time Delay Table 2
9
9-30
ENERVISTA MII PC
HMI
GENERAL
ADVANCED
GENERAL ADVANCED
SETTINGS
IDENTIFICATION
---
ACTIVE TABLE
Active Group
MIN TRIP TIME
Trip Min Time

9.24.2 PHASE / GROUND TOC SETTINGS (51P / 51G) (TABLE 2)

ENERVISTA MII PC
HMI
PHASE TOC
51P Function T2
51P
Enable T2
Enable 51P
51P Trip Permission T2 Trip Enable 51P
51P Pickup T2
Pickup 51P
51P Curve Type
Curve 51P
51P Time Dial T2
TD Mult 51P
51P Definite Time T2
Def Time 51P
51G Function
F51G
Enable T2
Enable 51G
51G Trip Permission T2 Trip Enable 51G
51G Pickup T2
Pickup 51G
51G Curve Type T2
Curve 51G
51G Time Dial T2
TD Mult 51G
51G Definite Time T2
Def Time 51G

9.24.3 PHASE / GROUND IOC SETTINGS (50P / 50G) (TABLE 2)

ENERVISTA MII PC HMI
50P Function T2
PHASE TOC 50P
Enable T2
Enable 50P
50P Trip Permission
Trip Enable 50P
T2
50P Pickup T2
Pickup 50P
50P Time Delay T2
Delay 50P
50G Function T2
GROUND IOC 50G
Enable T2
Enable 50G
50G Trip Permission
Trip Enable 50G
T2
50G Pickup T2
Pickup 50G
50G Time Delay T2
Delay 50G
MIGII Digital Protection for Electrical Machines
9 RELAY COMMISSIONING
9.24.1 GENERAL SETTINGS
VALUE RANGE
Text
1-2
50-300 ms
VALUE
RANGE
Y/N
Y/N
0.1-2.4 FLA (Ph)
INV, V.I., E.I., T.DE, USU
0.05 - 2.00 (IEC curves)
0.5 - 20.0 (ANSI curves)
0 - 600 s.
Y/N
Y/N
0.1 - 2.4 In (Gnd)
INV, V.I., E.I., T.DE, USU
0.05 - 2.00 (IEC curves)
0 - 600 s.
VALUE RANGE
Y/N
Y/N
0.1 - 30 FLA
0 - 600 s.
Y/N
Y/N
0.1 - 30 In (Gnd)
0 - 600 s.
STEP
NA
NA
1 ms
STEP
NA
NA
0.01
NA
0.01
0.01
0.01 s.
NA
NA
0.01 In (Gnd)
NA
0.01
0.01 s.
STEP
NA
NA
0.1
0.01 s.
NA
NA
0.1 In (G)
0.01 s.