Technical specifications
Article number
Total current of the outputs
•
Current per channel, max.
•
Current per group, max.
•
Current per module, max.
Total current of the outputs (per module)
horizontal installation
up to 60 °C, max.
–
vertical installation
up to 40 °C, max.
–
Cable length
•
shielded, max.
•
unshielded, max.
Encoder
Connectable encoders
•
2-wire sensor
permissible quiescent current (2-wire
–
sensor), max.
Interrupts/diagnostics/status information
Diagnostics function
Substitute values connectable
Alarms
•
Diagnostic alarm
•
Maintenance interrupt
•
Hardware interrupt
Diagnostic messages
•
Monitoring the supply voltage
•
Wire-break
•
Short-circuit
•
Group error
Diagnostics indication LED
•
RUN LED
•
ERROR LED
•
MAINT LED
Monitoring of the supply voltage (PWR-LED) Yes; via SIMATIC TOP connect connection module
•
•
Channel status display
•
for channel diagnostics
•
for module diagnostics
34
6ES7523-1BP50-0AA0
0.3 A
2 A
4 A
4 A
4 A
1 000 m
600 m
Yes
1.5 mA
No
No
No
No
No
No
No
No
No
Yes; green LED
Yes; red LED
No
Yes; via SIMATIC TOP connect connection module
No
No
Digital input/output module DI 32x24VDC SNK/SRC/DQ 32x24VDC/0.3A SNK BA (6ES7523-1BP50-0AA0)
Equipment Manual, 07/2020, A5E48027024-AA